Figure 4-12: Example of a Function Block Configuration of the Rosemount 2230 Using
DeltaV
In
Figure 4-12
devices installed on Tank 1: a Rosemount 2240S Multiple-input Temperature Transmitter
and a Rosemount 5900S Radar Level Gauge.
Product Level is output from the Rosemount 5900S via an Analog Input block to the
Multiple Analog Output Block 1 (FFMAO1) in the Rosemount 2230 display, as well as to the
Analog Output Block (FFAO_RMT7) in the Rosemount 2240S Temperature Transmitter,
for Average Product Temperature calculations.
Water Level and Average Product Temperature is output from the Rosemount 2240S via
Analog Input blocks to the Multiple Analog Output Block 1 (FFMAO1) in the Rosemount
2230 display.
Temperature from six elements is output from the Rosemount 2240S via a Multiple
Analog Input Block (FFMAI1) to the Multiple Analog Output Block 2 (FFMAO2) in the
Rosemount 2230 display.
The Rosemount 2230 display can be configured for output of measurement data by using
the AMS Device Manager.
Example of MAO block configuration using AMS Device Manager
In control strategy software, such as Control Studio, function blocks are connected to
various tank process variables. In AMS Device Manager the Guided Setup provides easy
access for configuration of function blocks that are available for the Rosemount 2230.
The Control Studio diagram in
to the Multiple Analog Output blocks in this example. MAO Block 1 and MAO Block 2 are
Rosemount 2230 Graphical Field Display
Control Studio Online
a Rosemount 2230 Graphical Field Display receives data from two field
Figure 4-12
Configuration and operation
shows which tank variables that are connected
March 2021
75