Table 5-4: Troubleshooting Chart for Tankbus Related Problems
Symptom
No communication
with the Rosemount
2230 Graphical Field
Display
Rosemount 2230 Graphical Field Display
Possible cause
Incorrect termination on
the Tankbus
Too many devices on the
Tankbus
Connection to Rosemount
2460 System Hub
Incorrect configuration of
Rosemount 2460 System
Hub
Service and troubleshooting
Action
Check that there are two terminators on
the Tankbus. Normally the built-in
termination in the Rosemount 2410 Tank
Hub is enabled.
Check that terminations are placed at
both ends of the Tankbus
Check that the total current consumption
of the devices on the Tankbus is less than
250 mA. See the Rosemount 2410
Reference Manual
(Document no.
00809-0100-2410) for more information.
Remove one or more devices from the
Tankbus. The Rosemount 2410 Tank Hub
supports a single tank. The multiple tank
version of the Rosemount 2410 supports
up to 10 tanks.
Check that the right field port on the
Rosemount 2460 System Hub is
connected to the Primary bus on the
Rosemount 2410 Tank Hub.
Check communication port LED:s inside
the Rosemount 2460 System Hub.
Check the Modbus communication
address specified for the appropriate ATD
device, i.e. the device that represents the
Rosemount 2240S Multi-input
Temperature Transmitter in the system
hub's tank database. For the single tank
version, this address is equal to the
Modbus address of the Rosemount 2410
Tank Hub itself.
Check configuration of communication
parameters for the Rosemount 2460
System Hub field ports.
Check that the correct communication
channel is selected.
See the Rosemount Tank Gauging
Configuration Manual
(Document no.
00809-0300-5100) for more information on
how to configure the system hub.