C. Timer used in the function block
Use the T412–T511 timers for the function block or the interrupt.
When the instruction TMR or END is executed, the timer used in the functional block begins to count.
When the value of the timer matches the timer setting value, the output coil is ON.
If you use the general-purpose timer is used in the function block or the interrupt, and the functional or
interrupt is not executed, the timer cannot count correctly.

5.2.10 16-bit Counters

Characteristics of the 16-bit counter
Item
Type
Number
Direction
Setting value
Specificying the counter setting
value
Change of the current value
Output contact
T1
T2
T1+T2=10 sec
SV: K100
General type
C0–C511
Counting up
0–32,767
The setting value can be either the constant or the value in the data
register.
The counter stops counting when the value of the counter matches the
setting value.
The contact is ON when the value of the counter matches the setting value.