9.4.5
Data Exchange – Implicit Message
When the connection between devices is established, you can use exchange data between devices. This section
provides an overview of how to create a data exchange table.
Network View
9.4.5.1 Data Exchange page
1. Data Exchange Table
No.
Category
Tool bar
Information
bar
Data
Data Exchange
Data Ex change
Table
Item
Add
Edit
Move Up / Move Down
Copy / Delete
Delete All
Sort By IP Address
Number of connections
Communication capacity
Communication
parameters
Enable
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Download
Set up
Description
Use this button to add new item for data exchange. Click the IP
address column of the newly added row to select the IP address
of the to-be-added device.
Use this button to open the data exchange table for editing.
Use this button to change the order of data exchange. (this order
is related to the order in SR1020 to SR1083, the EtherNet/IP
connection 1 to 32).
Use this button to copy or delete the selected row.
Use this button to delete the whole data exchange table.
Use this button to arrange the order of data exchange by IP
addresses.
CIP Connection Used: the total number of connections for
data exchange
TCP Connection Used: the total number of connected
devices
Connection for data exchange; each row represents one
independent EtherNet/IP connection. The number of connections
cannot exceed the maximum number of connections for the
Scanner. For example, AS Series can be connected to up to 16
adapters and the maximum number of connections for data
exchange is 32.
Enter the assumed PLC scan time to estimate the network loading
for the data exchange. Refer to section 9.3.2 for more information.
Display the essential parameters of the selected row.
Enable or disable the data exchange of the connection.