As-Fpfn02 Error Codes & How To Fix Them - Delta AS Series Operation Manual

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

Send Quote Requests to info@automatedpt.com
9.6.3 AS-FPFN02 Error Codes & How to fix them
9.6.3.1 LED Indicators
System Fail (SF) indicator RED light ON
Bus Fail (BF) indicator RED light BLINKING
Bus Fail (BF) indicator RED light ON
9.6.3.2 Status Registers of Siemens S7-1500
Status Register
(Siemens S7-1500)
Input Data Available
%I0.0
Connection Status
%I4.0 - %I4.7
Connection Status
%I5.0 - %I5.7
Description
If the value is TRUE, the input data is valid.
If the value is 0, the input data is invalid.
Check if the AS300 firmware version is V1.08 or higher.
Indicates PN connection status of Slot 1 ~ Slot 8.
If the value is TRUE, the Slot is with a working PN connection (with IO module)
If the value is FALSE, the Slot is without a working PN connection.
Indicates PN connection status of Slot 9 ~ Slot 16.
If the value is TRUE, the Slot is with a working PN connection (with IO module)
If the value is FALSE, the Slot is without a working PN connection.
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Check if the parameters downloaded to the Controller are the
same as the actual placement
1. Check if the upper device is well-connected
2. Check if the device name set in the software is the same as the
device name shown in the function card
3. Check if the MAC address and the device name are assigned
correctly
1. Check if the network cable is securely connected
2. Check if the controller and the function card are both supplied
with power
Description
Procedure