4.9.4 Wiring AS04DA-A

*2
AC m otor driv e,
recorder,
proportioning v alv e
AC motor driv e,
recorder,
proporti oni ng v al ve
*1. Use shielded cables to isolate the analog input signal cable from other power cables.
*2. If noise in the input voltage results in noise interference in the wiring, connect the module to a capacitor with
a capacitance between 0.1–0.47 μF with a working voltage of 25 V.
*3. Connect the SLD to FE. Connect FE and the terminal
*4. Every channel can work with the wiring shown above.
Voltage output
*4
- 10V~+1 0V
CHX
Shielded c able* 1
*4
Current output
CHX
0 mA ~20 mA
Shielded cable*1
*3
FE
24VDC
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
VO1
IO1
AG
A G
SL D
VO4
IO4
A G
A G
SLD
DC/DC
0 V
C on ve rte r
2 4V
to ground.