Wiring As06Rtd-A - Delta AS Series Operation Manual

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

Send Quote Requests to info@automatedpt.com

4.10.2 Wiring AS06RTD-A

Ω , 0~3000Ω
0~300
Ni100/Ni120/Ni1000/Pt100/Pt1000
Cu50/Cu100/JPt100/LG-Ni1000
Shielded c able*1
2-Wire
Shielded c able*1
3-Wire
*1. Use shielded twisted pair cables for temperature sensors and keep them away from power cables and
other cables that generate noise.
*2. Terminal "I12-" indicates " I1- & I2-", terminal "I34-" indicates " I3- & I4-", and terminal "I56-" indicates
" I5- & I6-". If you use two-wire temperature sensors, Ln- and In- must be short-circuited (where n is
between 1–6).
*3. There are two different internal excitation currents. If you are using temperature sensors, such as Ni100,
Ni120, Pt100, JPt100, Cu50/Cu100, or a 0~300 Ω resistance sensor, the internal excitation current is
1.0 mA. If you are using a Ni1000 temperature sensor, a Pt1000 temperature sensor, a LG-Ni1000
sensor, or a 0~3000 Ω resistance sensor, the internal excitation current is 0.2 mA.
Note: use cables with the same length (less than 200 m) and use terminal resistors of less than 200 ohm.
CH1
L1+
L1-
SL D
CH2
L2+
L2-
*2
I12-
A G
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Ni100, Ni120 ,
Pt 100, JPt 100,
Cu50, Cu1 00,
Ni1 000, Pt10 00,
LG-Ni1000 *3
ADC