13.3.4 Steps to Restore Delta Device Parameters

Two ways you can use to restore the Delta device parameters. One is to use ISPSoft to perform the restoration and the
other way is to send commands (SM/SR) to the SD card of the AS Series PLC CPU through HMI. Refer to section
3.1.4.16 Delta Device Parameters Backup and Restore from ISPSoft User Manual for more information. Here we focus on
the operation of sending commands (SM/SR) to the SD card of the AS Series PLC CPU through HMI.
Use SM/SR devices to appoint which Delta drive should be restored. Refer to the table below. After you have set the
configurations, the PLC executes the restorations when the PLC is Power-On or from Stop to Run.
SM / SR
SR1600
Parameter restoration code
SR1601.0
~
SR1601.15
Target device number to perform
and
parameter restoration
SR1602.0
~
SR1602.15
The total number of Delta drives that
SR1603
error has occurred during restoration
The last digit of the device's IP
SR1604
address that a most recent error
occurred during restoration
The error code of the last device that
SR1605
error occurred
SM1160
Parameter restoration complete
Error occurred during parameter
SM1161
restoration
Function
0: No action (default)
1: The AS Series PLC CPU executes the
restoration when the PLC is Power-On or from Stop
to Run. When the restoration is complete, reset the
value to 0.
SR1601.0: corresponding to target device #1
SR1601.1: corresponding to target device #2
SR1601.15: corresponding to target device #16
OFF: No action (default)
ON: Execute restoration on the appointed target
device.
0: No error occurred
1~16: The total number of Delta drives that error
has occurred during restoration
0 ~ 255: The last digit of the device's IP address
that a most recent error occurred during restoration.
(Only valid when SM1161 is switched to ON. Find
SM1161 description below.)
Refer to the error code table below.
OFF: When the value in SR1600 changes from 1 to
0, reset SM1160 to OFF.
ON: When the restoration is complete and
successful, SM1160 switches to ON.
OFF: When the value in SR1600 changes from 1 to
0, reset SM1160 to OFF.
ON: If any error occurred during restoration,
SM1161 switches to ON.
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Description
Retainable
Yes
Yes
No
No
No
No
No

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents