Error
Code
(16#)
The Internal factory calibration or
1608
the CJC is abnormal.
1609
-
Reserved (Error codes for the extension modules)
160F
200A
Invalid instruction
The number of MODBUS TCP
6010
connections exceeds the range.
The number of EtherNet/IP
6011
connections exceeds the range.
C000
-
The program syntax is incorrect.
CFFF

12.2.3 ERROR LED Indicators Blinking Rapidly Every 0.2 Seconds

The blinking happens when the power supply 24 VDC of the CPU module is disconnected, or the power supply is not
sufficient, not stable or abnormal.
Error
Code
(16#)
002A
The external voltage is abnormal.
12.2.4 ERROR LED Indicators Slow Blinking Every 3 Seconds and
Lighting up for 1 Second
Error
Code
(16#)
The converted value in the
function card 1 (AS-F2AD) or in
0040
the built-in AD input channel 1
exceeds the setting range.
The converted value in the
function card 1 (AS-F2AD) or in
0041
the built-in AD input channel 2
exceeds the setting range.
The converted value in the input
channel 1 of the function card 2
0042
(AS-F2AD) exceeds the setting
range.
The converted value in the input
channel 2 of the function card 2
0043
(AS-F2AD) exceeds the setting
range.
Description
module is normal.
If the problem persists, contact the local authorized
distributors.
Check the syntax error step in the program. Modify and
compile the program and then download the program
again.
Check the number of superior devices (maximum is 32).
Check the number of connections (maximum is 16).
Save the PLC program and hand the file to the company
or the technicians.
Description
Check whether the external 24 V power supply to the
module is normal.
Description
Check the actual input signal
Check the actual input signal
Check the actual input signal
Check the actual input signal
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Solution
Solution
Solution
Flag Log
SM10
V
SM5
V
SM
V
1092
SM
V
1093
Flag Log
SM7
V
Flag
Log
SM27
H
SM27
H
SM27
H
SM27
H

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents