When X0.0=ON, the instruction RST will be executed and the current value of C0 will be reset to zero and
the output contact of the counter C0 will be FF.
2.
When X0.1 is from OFF to ON, the value of the counter increases by one increment.
3.
When the value of the counter C0 reached the setting value 5, the contact of the counter C0 will be ON
(the current value of C0 = the setting value = 5). After that the trigger from X0.1 will not be accepted by
C0 and the current value of C0 will stay at the value 5.

5.2.11 32-bit Counters (HC)

Characteristics of the 32-bit counter
Item
Type
Number
Direction
Setting value
Specification of the
setting value
Change of the current
value
Output contact
Reset
X 0.0
X 0.1
C0 ( PV )
2
1
0
Y 0.0 ,C0
Up/down counter
HC0–HC63
Counting up/down
-2,147,483,648 to +2,147,483,647
The setting value can be either the constant or the value occupying two data
registers (32-bit).
The counter keeps counting even after the value of the counter matches the setting
value.
The contact is ON when the value of the addition counter matches the setting value.
The contact is reset to OFF when the value of the subtraction counter matches the
setting value.
When the RST instruction is executed, the current value is cleared to zero, and the
contact is reset to OFF.
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
5
4
(SV)
3
0
32-bit counter
Up counter
HC64–HC199
Counting up
High-speed counter
HC200–HC255
Counting up/down