4 I/O Data
4-1
Outline of I/O Data
This section introduces the I/O data of the IO-Link Master Unit.
4-1-1
Introduction to I/O Data and Types of I/O Data
The I/O data is the data for cyclic communications between the IO-Link Master Unit and the controller.
The following types of I/O data are available.
• Process input data from and process output data to each connected IO-Link devices (process da-
*1
ta)
• Digital inputs for pin 2, digital I/O data of the connected IO-Link devices
• IO-Link master status
*1. For the I/O data (process data) of OMRON IO-Link devices, refer to the Index List of the IO-Link devices in
Related Manuals on page 21.
4-1-2
Types of I/O Data
This section describes the types of I/O data.
The following I/O data is contained in the IO-Link Master Unit.
Input Data (from the IO-Link Master Unit to the Controller)
l IO-Link Master Status
Data name (= object
name)
Input Data Enabled
Flags
IO-Link Communica-
tions Module Proc-
essing Error
I/O Power On/Off Sta-
tus
I/O Port Error Status
4-2
Description
Indicates whether the IO-Link process
input data in IO-Link Mode is valid or
invalid at the controller for each port.
Indicates the error status of the IO-Link
communications processing section.
Indicates the status of the I/O power
supply to the IO-Link Master Unit.
Indicates the following errors for each
port.
IO-Link communications error, short-cir-
cuit in I/O cable, device configuration
verification error, device I/O size error,
PDO mapping error, error-level device
event, and warning-level device event
Default
Size
I/O allo-
cation
1 bit per
Yes
2 bytes
port
1 bit
Yes
1 bit
Yes
1 bit per
Yes
4 bytes
port
NX/GX-series IO-Link System User's Manual (W570)
IO-Link Master
Unit
NX
GX
2 bytes