Event name
Non-volatile Memory Checksum Error
Meaning
An error occurred in the control parameters.
Source
EtherCAT Master Function Mod-
ule
Error attrib-
Level
utes
Recovery
Effects
User program
Indicators
EtherCAT NET RUN
---
System-de-
Variable
fined varia-
None
bles
Cause and
Assumed cause
correction
Noise
Attached in-
None
formation
Precautions/
The emergency error code is 6330 hex.
Remarks
NX/GX-series IO-Link System User's Manual (W570)
Source details Slave
Minor fault
Error reset (after cycling Slave Unit power)
Continues.
Operation
EtherCAT NET ERR
Flashes at 1-s intervals.
Data type
---
Correction
Return the control parameters to
their default settings using re-
store parameters (1011 hex) of
the EtherCAT Slave Unit.
10 Troubleshooting for IO-Link Systems
Event code
14A00000 hex
Detection tim-
ing
Log category
System
The Slave Unit's I/O communications stop and the
outputs turn OFF.
EtherCAT LINK/ACT
---
Name
---
Prevention
Implement noise countermeas-
ures.
When estab-
lishing commu-
nications after
turning ON
power to the
Slave Unit