1 Introduction to IO-Link Systems
Function name
IO-Link communications
error detection
Detection of short-circuits
in I/O cables
Notification of input data
validity
Load rejection for control-
ler communications errors
IO-Link total communica-
tions lost frames
Digital input filter
Digital input collection
Backup and restoration of
parameter settings in IO-
Link devices
Event log
*1.
The IO-Link Master Unit with unit version 1.1 or later is required to use this function.
The following table shows whether or not functions can be used according to the IO-Link Master Unit
type and connection conditions.
1-26
This function detects I/O cable breaks, disconnections from
IO-Link device ports, error-level device events, device con-
figuration verification errors, and IO-Link device malfunc-
tions.
This function detects short-circuits in I/O cables.
The controller can use the Input Data Enabled Flags to de-
termine whether the IO-Link process input data for IO-Link
communications is valid.
This function turns OFF outputs from the IO-Link Master
Unit when an error occurs in communications with the con-
troller in IO-Link Mode or in an SIO Mode.
This prevents output operations with incorrect values when
a communications error occurs.
The IO-Link total communications lost frames can be read
from the CX-ConfiguratorFDT.
You can use this function to determine communications sta-
tus as affected by I/O cable noise or other factors.
You can remove the chattering and noise of the input signal
for digital inputs in SIO (DI) Mode or for digital inputs for pin
2 in IO-Link Mode.
When the input data changes without stabilization of the
state of the contact point due to chattering and noise, this
function prevents changes in data and stabilizes it.
In IO-Link Mode, this function reflects the specified bit data
*1
in the input data from the IO-Link device on the digital input
data of the IO-Link Master Unit.
One bit for each IO-Link port can be aggregated.
As a result, the bit data in the input data from the IO-Link
device can be aggregated into the digital input data of the
IO-Link Master Unit.
This function cannot be used in SIO (DI) Mode and SIO
(DO) Mode.
If you are using this function, you cannot perform digital in-
puts for pin 2.
This function is used to back up parameter settings in IO-
Link devices in the IO-Link Master Unit or restore them to
IO-Link devices.
This eliminates the need to set parameters again after re-
placing an IO-Link device.
This function records events, such as errors and status
changes, that occur in the IO-Link Master Unit and IO-Link
devices.
Description
¡: Can be used. Í: Cannot be used.
NX/GX-series IO-Link System User's Manual (W570)
Reference
4-1-2 Types of I/O
Data on page 4-2
7-3 Load Rejection
for Controller Com-
munications Errors
on page 7-10
7-4 IO-Link Total
Communications
Lost Frames on
page 7-12
7-5 Digital Input Fil-
ter on page 7-15
7-7 Digital Input Col-
lection on page
7-26
7-6 Backup and Re-
storation of Parame-
ter Settings in IO-
Link Devices on
page 7-16
10-2 Checking for
Errors and Trouble-
shooting with Tools
on page 10-22