Omron NX Series User Manual page 251

Io-link system
Hide thumbs Also See for NX Series:
Table of Contents

Advertisement

Event
Event code
name
84870000 hex
IO-Link
Communi-
cations
Module
Processing
Error
84A00000 hex
Slave Unit
Verification
Error
84790000 hex
Error-level
device
event
847A0000 hex
IO-Link
Communi-
cations Er-
ror
84860000 hex
Warning-
level Device
Event Flag
84820000 hex
IO-Link De-
vice Config-
uration In-
formation
Created
84850000 hex
I/O Power
Supply ON
Detected
NX/GX-series IO-Link System User's Manual (W570)
Meaning
A hardware failure
A hardware failure occurred.
occurred in the IO-
Link Communica-
tions Module.
An error occurred in
An error occurred in the control
Slave Unit verifica-
board.
tion.
An error-level event
Use CX-ConfiguratorFDT to
occurred in the IO-
confirm the IO-Link event code
Link device.
of the IO-Link device.
An error occurred in
The I/O cable is broken. Or,
IO-Link communica-
the IO-Link device is discon-
tions with a device.
nected from the port.
An IO-Link device has failed.
The communications are af-
fected by noise.
A warning-level
Use CX-ConfiguratorFDT to
event occurred in the
confirm the IO-Link event code
IO-Link device.
of the IO-Link device.
IO-Link device con-
IO-Link device configuration in-
figuration information
formation was created.
was created.
The I/O power sup-
The I/O power supply ON was
ply ON was detected
detected in several times.
in several times.
10 Troubleshooting for IO-Link Systems
M
Assumed cause
a
j
Level
I
M
O
Reference
P
n
i
b
rt
f
n
s
o
¡
page
10-47
¡
page
10-48
¡
page
10-49
page
¡
10-50
¡
page
10-51
¡ page
10-51
¡ page
10-52
10-29
10

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gx seriesNx-ilm400Gx-ilm08c

Table of Contents