7-2

Specifications of I/O Data

This section describes I/O data for the Digital Output Units.
7-2-1

Allocable I/O Data

This section describes the allocable I/O data in the Digital Output Unit.
An I/O entry mapping is assigned to the I/O allocation settings for the Digital Output Unit except the Unit
that supports output refreshing with specified time stamp.
In the Unit that supports output refreshing with specified time stamp, one I/O entry mapping for input
and one I/O entry mapping for output are assigned.
A specific I/O entry is assigned to the I/O entry mapping for each NX Unit model. These allocations are
fixed, so you cannot add others or change them.
An I/O entry means the I/O data described in this section. An I/O entry mapping means a collection of
I/O entries.
To assign the I/O allocation information of the NX Unit or Slave Terminal to an NJ/NX-series CPU Unit
or NY-series Industrial PC, use the I/O ports for the allocated I/O data.
However, for Slave Terminals, I/O ports may not be used depending on the type of communications
master or Communications Coupler Unit.
Refer to the user's manual for the connected Communications Coupler Unit for details on how to use
I/O data for Slave Terminals.
NX Units in Free-Run Refreshing or Synchronous I/O Refreshing
Two-point Output Units
Data name
Output Bit 00
Output Bit 01
NX-series Digital I/O Unit User's Manual (W521)
Description
The output set value for
BOOL
output bit 00.
The output set value for
BOOL
output bit 01.
Data
Default
I/O port
type
value
name
FALSE
Output Bit 00 7000 hex
FALSE
Output Bit 01
7 Digital Output Units
Subin-
Index
dex
01 hex
02 hex
7 - 5