10 Troubleshooting for IO-Link Systems
Event name
Device Configuration Verification Error
Meaning
The connected device is different from the IO-Link device registered for a port of the IO-Link Master.
Source
EtherCAT Master Function Mod-
ule
Error attrib-
Level
utes
Recovery
Effects
User program
System-de-
Variable
fined varia-
None
bles
Cause and
Assumed cause
correction
The connected device is different
from the IO-Link device regis-
tered for a port of the IO-Link
Master.
Attached in-
Attached information 1: Port where error occurred
formation
Precautions/
None
Remarks
10-46
Source details Slave
Minor fault
Reset error
Continues.
Operation
Data type
---
Correction
Connect the IO-Link device reg-
istered for the port of the IO-Link
Master.
1 hex: Port 1
2 hex: Port 2
3 hex: Port 3
4 hex: Port 4
5 hex: Port 5
6 hex: Port 6
7 hex: Port 7
8 hex: Port 8
Event code
847C0000 hex
Detection tim-
ing
Log category
System
Operation will continue.
In the port with the error, cyclic communications
with the IO-Link device are not correct.
Name
---
Prevention
Connect the IO-Link device reg-
istered for the port of the IO-Link
Master.
NX/GX-series IO-Link System User's Manual (W570)