Emerson Rosemount 3051S Series Manual Supplement
Emerson Rosemount 3051S Series Manual Supplement

Emerson Rosemount 3051S Series Manual Supplement

Pressure transmitter with foundation fieldbus protocol
Hide thumbs Also See for Rosemount 3051S Series:

Advertisement

Manual Supplement
00809-0200-4853, Rev AB
November 2017
Rosemount
with F
OUNDATION
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5
Operation and maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5
Advanced Pressure Diagnostics for Foundation Fieldbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 10
1.0
Overview
This manual is intended to be used as a supplement to the Rosemount™ 3051S Series Pressure
Transmitter with F
selected. This manual supplement provides information on configuring, installing, operating,
maintaining, and troubleshooting the Rosemount 3051S Series Pressure Transmitter with F
Fieldbus communications. See
Table 1. Device Driver Information
Release
date
July-17
Dec-08
Sep-01
1.
NAMUR Revision is located on the hardware tag of the device. Differences in level 3 changes, signified above by xx, represent minor product
changes as defined per NE53. Compatibility and functionality are preserved and product can be used interchangeably.
2.
F
that could correspond to NAMUR Revisions.
3.
Device driver file names use device and DD revision. To access new functionality, the new Device Driver must be downloaded. It is
recommended to download new Device Driver files to ensure full functionality.
3051S Series Pressure Transmitter
Fieldbus Protocol
™ Fieldbus Protocol Reference Manual when option code IT6 has been
OUNDATION
Device identification
NAMUR
NAMUR
hardware
software
(1)
(1)
revision
revision
1.0.xx
1.0.xx
N/A
N/A
N/A
N/A
Fieldbus device revision can be read using a F
OUNDATION
Table 1
and
Figure
1.
Device driver
identification
F
F
OUNDATION
OUNDATION
Fieldbus
Fieldbus
software
universal
revision
revision
3.00.01
6.1.2
1.11.9, 2.1.2
5.0.1
1.0.3
4.01
Fieldbus capable configuration tool. Value shown is minimum revision
OUNDATION
Review
instructions
Manual
Device
document
(2)(3)
revision
number
24
00809-0200-4801
23
00809-0200-4801
20
00809-0200-4801
OUNDATION
Review
functionality
Change
description
Updated Field
Diagnostics, Mass
Flow Removed
Multi-bit Alert
Reporting, Block
Instantiation,
Common
Software
Download
Initial Product
Release

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Rosemount 3051S Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Emerson Rosemount 3051S Series

  • Page 1 Transmitter with F ™ Fieldbus Protocol Reference Manual when option code IT6 has been OUNDATION selected. This manual supplement provides information on configuring, installing, operating, maintaining, and troubleshooting the Rosemount 3051S Series Pressure Transmitter with F OUNDATION Fieldbus communications. See Table 1 Figure Table 1.
  • Page 2: Product Recycling/Disposal

    Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 Figure 1. Transmitter Data Flow Measured process Micro FF communications output input Product recycling/disposal Recycling of equipment and packaging should be taken into consideration and disposed of in accordance with local and national legislation/regulations.
  • Page 3: Parameter Index

    Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 Parameter index Enter the Block Index of the parameter to be displayed. Custom tag Enter up to five characters to be displayed on the top line of the LCD display when this parameter is displayed.
  • Page 4: Host Timer Recommendations

    Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 Table 2. Network Parameters Network parameter Value Slot Time Maximum Response Delay Maximum Inactivity to Claim LAS Delay Minimum Inter DLPDU Delay Time Sync class 4 (1ms) Maximum Scheduling Overhead...
  • Page 5: Installation

    Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 Installation For complete configuration details using Fieldbus, reference the Rosemount 3051S F  OUNDATION Fieldbus Reference Manual. Operation and maintenance For operation and maintenance details using Fieldbus, reference the Rosemount 3051S F ...
  • Page 6: Measurement Troubleshooting

    17.5 V dc for FISCO) Sensor module • Check for obvious defects, such as a punctured isolating diaphragm or fill fluid loss, and if replacement is needed, contact the nearest Emerson Service Center. • Check for proper fill fluid characteristics. Communication troubleshooting Some host systems may ask for the device's capability level during commissioning.
  • Page 7: Alarms And Conditions

    Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 Note Use this section if other devices appear on the segment, communicate, and remain on the segment. If other devices don't appear on the segment, communicate, or stay on the segment, the electrical characteristics of the segment should be checked.
  • Page 8 Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 Table 6. Failure–Fix Now Alert label display Description Recommended action message 1. Replace the sensor module. FAIL Failure has been Sensor Module SENSOR detected in the sensor Failure...
  • Page 9: Service & Support

    Service support To expedite the return process outside of the United States, contact the nearest Emerson representative. Within the United States, call the Emerson Instrument and Valves Response Center using the 1-800-654-RSMT (7768) toll-free number. This center, available 24 hours a day, will assists with any needed information or materials.
  • Page 10 Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 Advanced Pressure Diagnostics for F OUNDATION Fieldbus Overview The Rosemount 3051S F Fieldbus Pressure Transmitter with Advanced Diagnostics Suite is an OUNDATION ™ extension of the Rosemount 3051S Scalable Pressure Transmitter and takes full advantage of the ™...
  • Page 11 Link Master device if this is a concern. SPM technology SPM is a unique technology developed by Emerson that provides a means for early detection of abnormal situations in a process environment. The technology is based on the premise that virtually all dynamic processes have a unique noise or variation signature when operating normally.
  • Page 12 Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 The device can provide the statistical information to the user in two ways. First, the statistical parameters can be made available to the host system directly via F...
  • Page 13 Therefore, Emerson cannot absolutely warrant or guarantee that SPM will accurately detect each specific condition under all circumstances.
  • Page 14 Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 SPM configuration and operation The following section describes the process of configuring and using the SPM diagnostic. (optional) SPM_MONITORING_CYCLE = [1 – 1440] minutes (see “Other SPM settings” on page...
  • Page 15: Alert Configuration

    Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 Figure 6. SPM Monitoring Cycle Effect on Statistical Values SPM_USER_COMMAND Select Learn after all parameters have been configured to begin the Learning Phase. The monitoring phase will start automatically after the learning process is complete. Select Quit to stop the SPM.
  • Page 16 Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 Figure 7 illustrates an example of the standard deviation, with its baseline value and alert limits. During the monitoring phase, the SPM will continuously evaluate the standard deviation and compare it against the baseline value.
  • Page 17 Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 SPM_STATUS Current state of the SPM diagnostic. Possible values for SPM status are as shown in Table Table 10. SPM Diagnostic Current State Status value Description Inactive User Command in “Idle”, SPM not Enabled, or the function block is not scheduled.
  • Page 18 Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 6.12 SPM configuration with EDDL For host systems that support Electronic Device Description Language (EDDL), using SPM is made easier with step-by-step configuration guidance and graphical displays. This section of the manual uses AMS Device Manager version 10.5 for illustrations, although other EDDL hosts could be used as well.
  • Page 19 Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 Figure 9. Example AI Function Block for Trending Standard Deviation in DeltaV Set the units and scaling for the function block as desired: XD_SCALE = 0 to 1 in H O (68 °F)
  • Page 20 Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 When adding a standard deviation for history collection in DeltaV, it is recommended that you not use the default data compression settings. By default, the DeltaV Historian will log a new data point only when the process value deviates by 0.01 or more.
  • Page 21 Figure 13. PIL Basics Testing at Emerson and other sites indicates that SPM technology can detect plugged impulse lines. Plugging effectively disconnects the transmitter from the process, changing the noise pattern received by the transmitter. As the diagnostic detects changes in noise patterns, and there are multiple sources of noise in a given process, many factors can come into play.
  • Page 22 Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 When the lines between the process and the transmitter start to plug through fouling and build-up on the inner surfaces of the impulse tubing or loose particles in the main flow getting trapped in the impulse lines, the time and frequency domain signatures of the noise start to change from their normal states.
  • Page 23 Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 However, there is a combination of factors that may affect the output of the DP transmitter under single plugged line conditions. If the impulse line is filled with an incompressible fluid, no air is present in the impulse line or the transmitter body, and the plug is formed by rigid material, the noise or fluctuation will decrease.
  • Page 24 Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 Flow versus level applications As previously described, flow applications naturally generate noise. Level applications without a source of agitation have very little or no noise, therefore making it difficult or impossible to detect a reduction in noise from the plugged impulse line.
  • Page 25 Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 Note The Plugged Impulse Line diagnostic capability in the Rosemount 3051S F Fieldbus Pressure OUNDATION Transmitter calculates and detects significant changes in statistical parameters derived from the input process variable.
  • Page 26 Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 Figure 20. Plugged Impulse Line Diagnostics Flow Learning/Verification Phase Phases X = Learning Cycle Y = Detecting Cycle Status = OK Start (Relearn) Compute Mean and Std Dev over Y...
  • Page 27: Basic Configuration

    Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 4. Steady process verification At the end of the verification phase, the PIL compares the last mean and standard deviation against the previous mean and standard deviation to determine if the process is at a steady state. If the process is at a steady-state, then the PIL moves into detection phase.
  • Page 28 Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 By default, the value of PLINE_AFFECT_PV_STATUS is “No”, meaning the quality of the pressure measurement will not be changed if PIL detects a plugged impulse line. Setting this parameter to Yes will cause the status quality to change to “Uncertain”...
  • Page 29 Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 So, for example, if the PLINE_SENSITIVITY is set to High, then a plugged impulse line will be detected if the standard deviation either increases by more than 40 percent above its baseline value, or decreases more than 60 percent below its baseline value.
  • Page 30 Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 This process needs to be repeated for each impulse line plugging condition that needs to be detected. For DP measurements, this should be done for both the high side and the low side impulse line.
  • Page 31 Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 PLINE_Learn_Sensitivity The PLINE_LEARNING_SENSITIVITY parameter provides very specific adjustments to the sensitivity during the learning phase. Most of the time, it is sufficient to use these default values: Insufficient Dynamics Check: Ignores the insufficient dynamic check if not selected. Use only when ...
  • Page 32 Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 Table 14. Corresponding EDDL Labels Foundation Fieldbus parameter name EDDL label(s) PLINE_ON Plugged Line PLINE_LEARN_LENGTH Learning Cycle PLINE_SENSITIVITY Detection Limit PLINE_AFFECT_PV_STATUS Affect PV Status PLINE_RELEARN User Command PLINE_AUTO_RELEARN...
  • Page 33 Manual Supplement Rosemount 3051S Series Pressure Transmitter 00809-0200-4853, Rev AB November 2017 Rosemount 3051S Series Pressure Transmitter...
  • Page 34 Dubai, United Arab Emirates Conditions of Sale page. +971 4 8118100 The Emerson logo is a trademark and service mark of Emerson Electric Co. DeltaV, Plantweb, Rosemount, Scalable, SuperModule, and Rosemount +971 4 8865465 logotype are trademarks of Emerson. RFQ.RMTMEA@Emerson.com...

Table of Contents