Installing A Fan Module - HPE ProLiant XL645d User Manual

Gen10 plus server
Table of Contents

Advertisement

Prerequisites
Before installing this option, be sure that you have the components included with the hardware option kit.
Procedure
1. Remove the power supply blank.
2. Install the power supply.
3. Connect the power cord to the power supply.
4. Power up the server.

Installing a fan module

WARNING: To reduce the risk of personal injury from hot surfaces, allow the drives and the internal system
components to cool before touching them.
The system supports 15 fan modules. If the system has one fan lesser than 15 during boot, the system will boot in the
Nonredundant Mode. If the missing fan is installed, the system will begin functioning in Redundant Mode. If any fans are
missing during power up, the system will be allowed to boot, but will be using an unsupported configuration.
CAUTION: For proper cooling, do not exceed two minutes with the chassis front door open. Exceeding two minutes
can lead to thermal damage or system shutdown.
If installing a hot-plug fan without powering down the system, the chassis front door must be closed within two numutes.
For fan module numbering, see Fan module numbering.
Prerequisites
Before installing this option, be sure that you have the components included with the hardware option kit.