Site Requirement Guidelines

AC-Powered Routers

Figure 2-7
AC Power Cord Plugs and Appliance Coupler
North America
Rewirable twist-lock plug
NEMA L6-20P (20A)
Italy
1/3/16 plug
CEI 23-16 (16A)
Cisco 12016, Cisco 12416, and Cisco 12816 Router Installation and Configuration Guide
2-18
AC PEMs operate in the nominal range of 200 VAC to 240 VAC and require a
minimum service of:
20 A for operation in North America
16 A for international operation
13 A for operation in the UK
Each of the AC power inputs requires separate dedicated branch circuit. For a list
of the nominal and acceptable value ranges for source AC power, refer to
Table A-2 on page
A-3.
Figure 2-7
shows different styles of AC power cords used to connect to the local
AC power source that are available for North America and various locales.
Australia, New Zealand
SAA/3 plug
AS/NZZS 3112-1993 (15A)
United Kingdom
BS89/13
BS 1363/A
(13A; replaceable fuse)
Chapter 2
Preparing for Installation
Europe, Argentine, Brazil
VIIG plug
CEE (7) VII (16A)
Appliance coupler
C19W coupler
Hot EN60320/C19 (20A)
OL-11495-01