Exhaust from other equipment vented directly into the Cisco 12404 Internet
router air inlet may cause an over-heat condition. Install the router so that it is
protected from a direct flow of hot air from other equipment.
At sites where the Cisco 12404 router operates with AC PEMs, observe the
following guidelines.
A power factor corrector (PFC) allows the PEM to accept AC power source
•
voltage from an AC power source operating between 100–120 VAC, 15–Amp
service in North America; and a range of 185–264 VAC, 10–Amp service, in
an international environment.
All AC PEM power cords measure 14 feet (4.3 meters).
•
Provide a dedicated power source for each PEM installed in the router.
•
Install an uninterruptable power source where possible.
•