Zone Button Operation

Each zone column (LEDs and buttons)
represents one zone of lights. Pressing
any button on a column turns on the info
screen and displays the zone's current
light level and current energy savings.
Pressing the raise and lower buttons on a
zone causes different actions depending
on zone type (see below).
Dimmable zones:
• Press and hold to raise/lower all lights in a
zone; release to stop
• Press raise or lower to stop a zone that is
fading
• Raising lights from off to full on or lowering
from full on to off takes 5 seconds
• Press raise and lower simultaneously to
toggle between full on and off
• Press and hold lower for 6 seconds after
the zone has gone to 0% light level to
set the zone as unaffected in the current
scene. The zone will not change when this
scene is initiated, and the Master buttons
will not raise/lower the zone in this scene.
Non-dim zones:
• Press raise to turn zone on
• Press lower to turn zone off
Note: To set zone types, see the zone
setup section.
®
Zone LEDs
LEDs indicate
light level
(see below)
Zone Raise
Zone Lower

Zone LED Displays for % of Lighting Levels

Light Level
Off
1–17
(%)
Dimmable
Load Types
Non-Dim
Load Types
Legend:
UA = Unaffected (lights are not affected by
scene button or Master buttons)
LED lit
LED off
GRAFIK Eye
18-33
34-49
50-66
67-82
QS Control Unit Installation and Operation Guide 14
®
83-99
On/
UA
100