Qs Link Control Wiring Details - Lutron Electronics GRAFIK Eye QSGRN-6PCE Installation And Operation Manual

Table of Contents

Advertisement

Wiring the GRAFIK Eye

QS Link Control Wiring Details

• System communication uses IEC PELV/NEC
Class 2 wiring.
• Follow all local and national electrical codes when
installing IEC PELV/NEC
voltage/mains wiring.
• Each terminal accepts up to two 1.0 mm
• Total length of control link must not exceed 610 m.
• Make all connections in the control unit's wallbox.
• Wiring can be T-tapped or daisy-chained.
• IEC PELV/NEC
Class 2 24 V
®
System Limits
The QS wired communication link is limited to 100
devices or 100 zones.
The GRAFIK Eye
QS control unit supplies 3 Power
®
Draw Units (PDUs) on the QS link. Refer to the
QS Link Power Draw Units specification submittal
(Lutron PN 369405) for more information concerning
Power Draw Units.
Wire Sizes (check compatibility in your area)
QS Link Wiring Length
Less than 153 m
153 to 610 m
®
QS Control Unit:
®
®
Class 2 wiring with line
®
wires.
2
150 mA.
Wire Gauge
Power (terminals 1 and 2)
1 pair 1.0 mm
2
Data (terminals 3 and 4)
1 twisted, shielded pair 0.5 mm
Power (terminals 1 and 2)
1 pair 4.0 mm
2
Data (terminals 3 and 4)
1 twisted, shielded pair 0.5 mm
LUTRON
LUTRON
GRAFIK Eye
control unit
QS smart
power
panel
Sivoia
QS
®
window
treatment
Daisy-Chain Wiring Example
GRAFIK Eye
QS
®
control unit
LUTRON
Lutron Cable Part Number
GRX-CBL-346S
GRX-PCBL-346S
2
GRX-CBL-46L
GRX-PCBL-46L
2
GRAFIK Eye
QS Control Unit Installation and Operation Guide 8
®
LUTRON
LUTRON
LUTRON
LUTRON
T-Tap Wiring Example
seeTouch
wallstation
QS
®
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
Sivoia
®
QS
GRAFIK Eye
QS
window
®
control unit
treatment
LUTRON
LUTRON
LUTRON
QS smart
power panel
LUTRON
LUTRON
LUTRON
LUTRON
QS
®
seeTouch
QS
®
wallstations
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON

Advertisement

Table of Contents
loading