Cci Type Settings - Lutron Electronics GRAFIK Eye QSGRN-6PCE Installation And Operation Manual

Table of Contents

Advertisement

Contact Closure Input (CCI) Setup (continued)
(wired directly to the GRAFIK Eye
The integral contact closure input (CCI) on the back of the GRAFIK Eye
is compatible with either type of contact closure device:
Maintained (default): The GRAFIK Eye
closure and a contact open/release event.
Example: CCI Mode set to Afterhours. Contact closure starts Afterhours. Contact
open/release ends Afterhours.
Momentary: The GRAFIK Eye
Example: CCI Mode set to Afterhours. Contact closure starts Afterhours. Contact
open/release has no effect. Second contact closure ends Afterhours.
Changing the type of contact closure input:
1. Enter programming mode.
Main menu
2. Use the Master buttons to highlight "CCI Setup" and press the
Save Mode
OK button to accept.
CCI Setup
3. Use the Master buttons to highlight "CCI Type" and press the
OK button to accept.
4. Use the Master buttons to highlight the type you wish the CCI to
CCI menu
control. Press the OK button to accept.
5. The info screen will confirm that your setting has been saved.
CCI Mode
6. Exit programming mode.
CCI Type
Note: The Emergency CCI Mode is different from the other CCI
CCI Type
Maintained
Saved
Saved
®
QS control unit)
®
QS control unit will act on both a contact
®
QS control unit will act on only contact closure events.
®
modes in that Emergency Mode will activate on a contact
open/release and will deactivate on a contact closure.
The CCI must be set to Maintained (default) for proper
Emergency Mode operation.
QS control unit
®
GRAFIK Eye
QS Control Unit Installation and Operation Guide 25
®
Master
buttons
OK
OK
button
Timeclock
(back) button