Afterhours - Lutron Electronics GRAFIK Eye QSGRN-6PCE Installation And Operation Manual

Table of Contents

Advertisement

Afterhours

The Afterhours feature of the GRAFIK Eye
"Scene Off"). This feature allows occupants to manually turn on lights, but will automatically turn them off after a specified amount of
time.
When Afterhours starts, the lights will flash to alert occupants that the lights will soon fade to the Afterhours Scene. Occupants then
can press a keypad button to extend the time until the Afterhours feature flashes the lights again.
The Afterhours feature of the GRAFIK Eye
• Enabled: The GRAFIK Eye
• Follow: The GRAFIK Eye
• Disabled (default): The GRAFIK Eye
Timeclock event, contact closure input, or another device on the QS link).
Note: The Afterhours feature must be programmed to start or end through Timeclock events, the integral contact closure input, or
another associated device on the QS link. The GRAFIK Eye
has been set to "Enabled" or "Follow".
Afterhours Settings
Flash count: The amount of times the lights will flash to alert the room that the Afterhours Scene will soon be activated.
Range: 0 to 15 flashes (default 3 flashes)
Delay time: The amount of time after the end of the "Flash count" before the Afterhours Scene is activated.
Range: 1 to 180 minutes (default 15 minutes)
Warn time: The amount of time the system will wait after the Afterhours Scene is interrupted before flashing the lights again and
restarting the Delay Time countdown.
Range: 1 to 180 minutes (default 5 minutes)
Afterhours scene: The scene that the GRAFIK Eye
Range: Scenes 1 to 16, Off (default Scene 5)
(See example on the next page.)
®
QS control unit can be used to automatically set lights to an energy-saving level (typically
®
QS control unit has three (3) modes of operation:
®
QS control unit will allow the Afterhours feature to be activated.
®
QS control unit will execute the Afterhours settings of another associated device on the QS link.
®
QS control unit will not start the Afterhours feature (even if it receives commands from a
®
®
QS control unit will activate this feature only if the Afterhours mode
®
QS control unit will activate when the Delay Time expires.
GRAFIK Eye
QS Control Unit Installation and Operation Guide 56
®

Advertisement

Table of Contents
loading

Table of Contents