Timeclock Operation

Adding an Event

Main menu
1. Enter programming mode.
2. Use the Master buttons to highlight "Timeclock" and press the
Timeclock
Timeclock
OK button to accept.
Scene setup
3. Use the Master buttons to highlight "Add events" and press
the OK button to accept.
4. Use the Master buttons to highlight the recurrence for this event: day of the week, holiday, weekdays or
Timeclock
weekends. Press the OK button to accept.
View events
5. Use the Master buttons to highlight the location of the timeclock event (local or remote). Press the OK
button to accept.
Add events
• L ocal events affect scenes controlled by the GRAFIK Eye
• R emote events affect scenes controlled by another device on the QS link (e.g. Energi Savr Node
Note: R emote timeclock events provide a virtual timeclock to devices on the QS link without a built-in
Add events
Monday
6. Use the Master buttons to highlight the type of the event (fixed time of day or a relative time to sunrise or
sunset). Press the OK button to accept.
7. F or a fixed-time event, use the Master buttons to highlight the hour for your event to begin; press the OK
button to accept. Repeat for the minutes.
Add events
For a relative time event, use the Master buttons and the OK button to set the hour, then the minutes
relative to sunrise or sunset (maximum of 1 hour, 59 minutes before or after sunrise or sunset).
Local
8. Use the Master buttons to highlight the desired action for the timeclock event:
• Scenes 1-16, Off
• Shade (Window Treatment) Groups 1-3 open, preset, or close
• Start/End Afterhours
Add events
• Enable/Disable Occupancy
• Enable/Disable Occupied Events
• Enable/Disable Daylighting
Time of day
9. The info screen will confirm that your event has been saved.
10. Repeat steps 4 through 9 for additional events.
11. Exit programming mode.
Set time
Add events
Scene
: 00 AM
08
®
1
timeclock. This allows the GRAFIK Eye
affecting the space it controls.
Saved
Scene 1
2
3
4
5
6
®
QS control unit to activate scenes on other devices without
®
GRAFIK Eye
QS Control Unit Installation and Operation Guide 52
®