Powering More Than 3 Wallstations Example - Lutron Electronics GRAFIK Eye QSGRN-6PCE Installation And Operation Manual

Table of Contents

Advertisement

Wiring the GRAFIK Eye

Powering More Than 3 Wallstations Example

The GRAFIK Eye
QS control unit can power up to 3 seeTouch
®
more than three wallstations.
• The +24 VDC wire from the power supply
connects to QS link terminal 2 on all of
the wallstations it is powering. This wire
does not connect to terminal 2 on the
GRAFIK Eye
QS control unit.
®
GRAFIK Eye
QS control unit
®
(rear view)
®
QS Control Unit:
®
• The Common wire from the power
supply connects to QS link terminal 1
on all of the wallstations it is powering
and terminal 1 on the GRAFIK Eye
control unit.
Lutron cable
GRX-CBL-346S-500 or
GRX-PCBL-346S-500
1 twisted pair
0.5 mm
2
(1) 1.0 mm
2
Common
QSPS-P1-1-50
(powers up to 8 seeTouch
wallstations)
To power source
wallstations. An external 24 V
®
QS
®
seeTouch
QS wallstations
®
QS
®
GRAFIK Eye
QS Control Unit Installation and Operation Guide 10
®
power supply is required to power
• The communication signals on the QS
link (terminals 3 and 4) connect from
the wallstations to the GRAFIK Eye
control unit on twisted, shielded cable
just as when an additional power supply
is not being used. Control unit shown in
rear view.
QS
®

Advertisement

Table of Contents
loading

Table of Contents