9.4.6
Steady State AC Tests
Scroll to the NORMAL ST MENU entry using the up and down cursor keys. Press the ENTER
key to select the STEADY STATE screens. The screen will appear as shown in Figure 9-12
The MIL704 Steady state screens have the following tests:
1. VOLTAGE
2. FREQUENCY
3. VOLT UNBALANCE
4. PHASE DIFFERENCE
5. VOLT MODULATION
6. FREQ MODULATION
7. VOLT TRANSIENT
8. FREQ TRANSIENT
9. DISTORTION
The above tests can be selected by scrolling to the highlighted selection using the up and down
cursor keys and the ENTER key to start the selected test.
VOLTAGE
This test will change the output voltage in the sequence shown in Table 9-12.
SEQUENCE
The ← key (backspace) will terminate the test at any time.
FREQUENCY
MX15
Figure 9-12: Steady State Menu
VOLTAGE
400Hz/VFREQ
1
108
2
118
3
115
Table 9-12: Steady state voltage
TIME
60Hz only
110
1 minute
125
1 minute
115
1 minute
151