Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 Part. 1 General information 1. Model Names of Indoor/Outdoor Units ........2 2. External Appearance ............. 2 3. Nomenclature ............... 3 4. Product features ..............4...
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz 1. Model Names of Indoor/Outdoor Units Nominal Indoor unit Outdoor unit Capacity Model Power supply Model Power supply 1.5ton MTA-18WN1 220-240V~, 50Hz, 1Ph MOVTB-18CN1-13C 220-240V~, 50Hz, 1Ph 2ton MTA-24WN1 220-240V~, 50Hz, 1Ph...
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 2.2 Outdoor unit 3. Nomenclature 3.1 Indoor unit: M T A – 18 W N1 Refrigerant Type - N1: R410A Control Type: Wired controller Nominal Cooling Capacity (18×1,000Btu/h) Series Number: A type...
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz 4. Product features Indoor Unit General These duct type indoor units which capacity range is from 1.5ton to 5ton, are suitable for mounting above ceiling. The units are factory assembled, internally wired and tested before leaving the manufacture.
Page 7
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 Casing Unit casing is constructed of zinc coated, heavy gauge, and galvanized steel. Exterior surfaces shall be cleaned, G90 galvanized heavy gauge plate conforming to ASTMA 653, followed by baked on electrostatic polyester dry powder coat paint on all external panels, completely weatherized for outdoor installation and properly reinforced and brazed.
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 1. Features Full capacity range: 1.5ton, 2ton, 3ton, 4ton and 5ton. Suitable for using refrigerant R410A. Tropical design with Copeland compressor. Blue hydrophilic fin and inner grooved copper pipe.
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 Model MTA-60WN1 Matched outdoor unit MOVTB-60CN1-R13C Power wire (Indoor unit) 3×2.5mm Connecting wire Signal wire 2×0.75mm Ф25 Drain pipe size (OD) Controller Optional (220V signal reserved) Operation temperature ° C 18 - 30 Dimension (W×H×D)
Page 22
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz Top view Left side view...
Page 23
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 MTA-24WN1, MTA-36WN1 (Unit: mm) Air outlet side view Air inlet side view Top view...
Page 24
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz Left side view (Unit: mm) Outline dimension Air outlet opening size Model MTA-24WN1 1,140 1,230 MTA-36WN1 1,140 1,230 (Unit: mm) Air return opening size Size of mounted lug Fresh air inlet Model Φ125...
Page 25
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 MTA-48WN1, MTA-60WN1 (Unit: mm) Air outlet side view Air inlet side view Connecting pipe side view...
Page 26
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz Top view A view...
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 8. Fan performance MTA-18WN1 In.H 0.05 0.15 0.25 0.35 12.5 24.9 37.4 49.8 62.3 74.7 87.2 Medium volume 1,003 High 1,306 1,219 1,125 1,029 Notes: ESP: External static pressure. The values are based the unit with filter operating under cooling mode.
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 11. Accessories Name Qty. Purpose Installation manual Pipe insulation material Heat insulation Water outlet joint For drainage Chucking the joint which connect Clap the drain hose and the outlet of...
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 1. Specifications Model MOVTB-18CN1-13C Power supply 220 - 240V~, 1Ph, 50Hz Ambient temperature in cooling ° C 17 - 54 Rated input 2,400 Rated current 11.5 Model ZP20KSE-PFZ-522 Type Scroll...
Page 52
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz Continued: Model MOVTB-18CN1-13C Power wire (Outdoor unit) 3×2.5mm Connection wire Signal wire 2×0.75mm Dimension (W×H×D) 554×633×554 Packing (W×H×D) 585×662×582 Net / Gross weight 55/58 Notes: 1. The nominal T1 cooling capacities are based on the following conditions: Indoor temperature: 27°...
Page 53
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 Model MOVTB-24CN1-13C Power supply 220 - 240V~, 1Ph, 50Hz Ambient temperature in cooling ° C 17 - 54 Rated input 3,000 Rated current 14.5 Model ZP25KSE-PFZ-522 Type Scroll Quantity Brand...
Page 54
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz Continued: Model MOVTB-24CN1-13C Power wire (Outdoor unit) 3×2.5mm Connection wire Signal wire 2×0.75mm Dimension (W×H×D) 600×633×600 Packing (W×H×D) 628×662×628 Net / Gross weight 59/62 Notes: 1. The nominal T1 cooling capacities are based on the following conditions: Indoor temperature: 27°...
Page 55
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 Model MOVTB-36CN1-13C Power supply 220 - 240V~, 1Ph, 50Hz Ambient temperature in cooling ° C 17 - 54 Rated input 4,000 Rated current Model ZP36KSE-PFZ-522 Type Scroll Quantity Brand Copeland...
Page 56
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz Continued: Model MOVTB-36CN1-13C Power wire (Outdoor unit) 3×4.0mm Connection wire Signal wire 2×0.75mm Dimension (W×H×D) 710×759×710 Packing (W×H×D) 738×779×738 Net / Gross weight 86/90 Notes: 1. The nominal T1 cooling capacities are based on the following conditions: Indoor temperature: 27°...
Page 57
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 Model MOVTB-36CN1-R13C Power supply 380-415V~, 50Hz, 3Ph Ambient temperature in cooling ° C 17 - 54 Rated input 4,000 Rated current Model ZP36KSE-TFM-522 Type Scroll Quantity Brand Copeland Capacity Btu/h...
Page 58
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz Continued: Model MOVTB-36CN1-R13C Power wire (Outdoor unit) 5×2.5mm Connection wire Signal wire 2×0.75mm Dimension (W×H×D) 710×759×710 Packing (W×H×D) 738×779×738 Net / Gross weight 81/85 Notes: 1. The nominal T1 cooling capacities are based on the following conditions: Indoor temperature: 27°...
Page 59
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 Model MOVTB-48CN1-R13C Power supply 380-415V~, 50Hz, 3Ph Ambient temperature in cooling ° C 17 - 54 Rated input 6,000 Rated current Model ZP51KSE-TFM-522 Type Scroll Quantity Brand Copeland Capacity Btu/h...
Page 60
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz Continued: Model MOVTB-48CN1-R13C Power wire (Outdoor unit) 5×2.5mm Connection wire Signal wire 2×0.75mm Dimension (W×H×D) 710×843×710 Packing (W×H×D) 738×862×738 Net / Gross weight 89/93 Notes: 1. The nominal T1 cooling capacities are based on the following conditions: Indoor temperature: 27°...
Page 61
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 Model MOVTB-60CN1-R13C Power supply 380-415V~, 50Hz, 3Ph Ambient temperature in cooling ° C 17 - 54 Rated input 7,450 Rated current Model ZP61KCE-TFD-522 Type Scroll Quantity Brand Copeland Capacity Btu/h...
Page 62
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz Continued: Model MOVTB-60CN1-R13C Power wire (Outdoor unit) 5×2.5mm Connection wire Signal wire 2×0.75mm Dimension (W×H×D) 740×843×740 Packing (W×H×D) 768×862×768 Net / Gross weight 98/102 Notes: 1. The nominal T1 cooling capacities are based on the following conditions: Indoor temperature: 27°...
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz 1. Notes WARNING: Failure to observe a warning may result in death. Be sure only trained and qualified service personnel to install, repair or service the equipment. Improper installation, repair and maintenance may result in electric shocks, short-circuit, leaks, fire or other damage to the equipment.
Page 71
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 If the power wire is damaged, it must be replaced by the manufacture or its service agent or similarly qualified person in order to avoid a hazard. An all-pole disconnection switch having a contact separation of at least 3mm in poles should be connected in fixed wiring.
Page 72
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz Connect the outdoor unit wires, and then connect the indoor unit wires. You are not allowed to connect the air conditioner with the power source until wiring and piping of the air conditioner is done.
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 Installation the connecting pipe Connect the drain pipe; Wiring; Test operation. At delivery, the package of indoor and outdoor units should be checked and any damage should be reported immediately to the service agent.
Page 74
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz the specific procedures. Cut off the roof beam. Strengthen the place cut off, and consolidate the roof beam. Carry out the pipe and line operation in the ciling after finishing the installation of the main body.
Page 75
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 MTA-48WN1, MTA-60WN1: (Unit: mm) When the pandant bolt is fixed in wooden structure, please put the square timber traversely over the roof beam, then install the hanging screw boltes.
Page 76
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz For steel roof beam structre, install and use directly the supporting angle steel. Overhang the indoor unit onto the hanging screw bolts with block. Position the indoor unit in a float level by using the level indicator, otherwise it may cause water leakage.
Page 77
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 MTA-18WN1 (Unit: mm) View of air outlet side View of air inlet side from rear (Default) View of air inlet side from down (Optional) MTA-24WN1, MTA-36WN1 (Unit: mm) View of air outlet side...
Page 78
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz View of air inlet side from rear (Default) View of air inlet side from down (Optional) MTA-48WN1, MTA-60WN1 (Unit: mm) View of air outlet side...
Page 79
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 View of air inlet side 2.3 Install the drainage pipe In order to prevent faults caused by condensate of the refrigerant pipe and drain pipe, perform condensate prevention and heat insulation properly.
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz In case of prolonged drainage pipe, you had beeter tighten its indoor part with a protection tube to prevent it from loosing. The end of the drainage pipe should be over 50mm higher than the ground or the bottom of the drainage chute, and do not immerse it in water.
Page 81
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 If the supply cord is damaged, it must be replaced by the manufacture or its service agent or a similarly qualified person in order to avoid a hazard. ...
Page 82
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz clearance for air entrance to the condenser coil, for air discharge and for service access. Notes: L1=1,000mm, L2=915mm. For multiple unit installations, units must be spaced a minimum of 915mm apart. (Coil face to face.
Page 83
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 strain on the refrigerant lines and possible leaks. Install the unit in a level position. Normal operating sound levels may be objectionable if the unit is placed directly under windows of certain rooms, such as bedrooms, study rooms.
Page 84
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz proper oil return. Factory-preferred tie-down method: Prior to installing clear pad of debris. Then cement pad must meet local codes and must be the proper thickness to accommodate fasteners.
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 4. Connection of Refrigerant Pipe Refrigerant pipe sizing between indoor and outdoor unit. Liquid Line Size - Outdoor unit higher than indoor unit Total Equivalent Length (m) Model Liquid /gas pipe (mm) 7.62...
Page 86
Incomplete insulation may cause water condensation. For MTA-18WN1, after connecting two pipes with copper nuts which are packed in indoor unit accessory to indoor unit, another pipe packed in indoor unit accessory should be welded with the gas connecting pipe of indoor unit.
Page 87
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 Braze the liquid line to the liquid valve at the outdoor unit. Be sure to wrap the valve body with a wet rag. Allow the nitrogen to continue flowing. Refer to the refrigerant pipe size list for proper liquid line sizing.
Page 88
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz filter. Care must also be taken to isolate the refrigerant pipes to minimize noise transmission from the unit the structure. The suction line must be insulated. Tape and suspend the refrigerant lines as shown in following figure.
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 Repair the leak and test again. To verify that the system has no leaks, simply close the valve to the vacuum pump suction to isolate the pump and hold the system under vacuum. Watch the micron gauge for a few minutes.
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz and drainage pipe to prevent water leak. 6. Electric Connection 6.1 Caution Power supply of indoor unit and outdoor unit must be within normal voltage range. Power wiring, control wiring, disconnect switches and over-current protection must be supplied by the installer.
Page 91
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 general, it is not allowed to parallel connection two wires, unless welding joint is well welded and wrapped with insulating tape. Every pole of the all-pole disconnection device should have at least 3mm separation distance and a leakage protector with the rating current above 10mA shall be installed together when wiring.
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MTA-36WN1 + MOVTB-36CN1-R13C, MTA-48WN1 + MOVTB-48CN1-R13C MTA-60WN1 + MOVTB-60CN1-R13C 7. Trial Run The trial run must be carried out after the entire installation has been completed. Please confirm the following points before the trial run: ...
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 8. Trouble shooting Outdoor unit’s malfunction and protection codes Content LED1 LED2 LED3 Power supply phase sequence error Flashing Extinguished Extinguished Lack of Phase A, B of power supply...
Page 96
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz Low pressure protection Notes: Low pressure protection is triggered 3 times in 20 minutes, the units should be repower again to reset the unit.
Page 97
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 Over-current protection of compressor Communication error (Reserved) Pipe temperature sensor (T3) error & Ambient temperature sensor (T4) error...
Page 98
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz High pressure protection & Discharge temperature protection...
Page 99
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 High temperature of condenser protection There is only one temperature is fixed in the indoor units with other thermostat, so these indoor units without PCB board have not any error or protection code to display.
Page 100
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz Content Display content Pipe temperature sensor (T2) error Operation lamp flashing Room temperature sensor (T1) error Timer lamp flashing Eeprom error Operation and timer lamp flashing Operation lamp flashing: Pipe temperature sensor (T2) error ...
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 9. Maintenance 9.1 Operation required before leaving the unit idle for a long period. Let the air conditioner run in the fan mode for about half a day, and let its interior be fully dry.
Page 102
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz Take off the motor. Clean the evaporator and fan, or change the indoor motor. 9.4 Tray maintenance (Only available for Model: 48 and 60 indoor unit) Shut down the unit and cut off power supply before maintain.
Page 103
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 removed first, as well as connective wires between motor and capacity of motor assembly. Fan motor subassembly is very heavy, please be careful during maintaining, otherwise physical injury would be caused.
Page 104
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz After motor maintenance, re-install the fan motor assembly as per reverse above orders, and connect the motor with electric control box, as well as motor with power cable of motor capacity.
Page 105
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 conditioner will be degraded. Therefore, clean it often if the air conditioner already has been used for a long period. If the indoor unit is installed in a place with heavy dust, clean the filter more often.
Page 107
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 1. Wired Controller: KJR-12B/DPC(T)-E (Customized) KJR-12B/DPC(T)-E 1.1 Remote controller specifications Model KJR-12B/DBC(T)-E Power supply voltage 5.0V DC Ambient temperature range -15° C~43° C Ambient humidity range RH40%~RH90% Performance Features 1. Operating mode: Cool, heat (Reserved), dry, fan and auto.
Page 108
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz 1.2 Introduction of function buttons on the wired controller ① MODE button: It is used to select mode, push the button one time, then the operation modes will change in turn as follows: Notes: No heating mode is reserved.
Page 109
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 ▼ minute part flashes every 0.5 seconds, then push ▲ or to adjust minute. When set clock or alter clock setting, must push the OK button to complete the setting.
Page 110
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz 1.3 Names and functions of indicators on wired controller ① Mode Display: Press MODE button can select ‘AUTO’, COOL’, ‘DRY’, ‘HEAT’ and ‘FAN’ mode. Notes: HEAT is reserved. ② Fan Speed Display: Press FAN SPEED to select fan speed from ‘AUTO’, ‘LOW’, ‘MED’, to ‘HIGH’.
Page 111
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 1.4 Operating the wired controller AUTO Operation ※ Insert the power supply of indoor unit, and operation lamp of indoor unit will flash. ※ Push MODE to select AUTO. ※ Set the desired temperature by pushing the TEMP ▲ and TEMP ▼, usually the temperature range is set from 17°...
Page 112
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz ※ Push the ON/OFF, the operation lamp of indoor unit lights, and the air conditioner will start to dehumidify. ※ Press the ON/OFF again, stop the air conditioner. Notes: The FAN SPEED and ECONOMICAL buttons are invalid in the dry mode.
Page 113
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 ※ Push button TIME OFF again, and then adjust the time of timer off as desired. ※ When set the timer on and timer off simultaneously, if the setting times of timer on and timer off are less than 10 hours, then timer off time will always 0.5 hours later than the...
Page 114
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz ※ After enter into the setting interface, the temperature display area will display YX. Y means the first function code, and X means the second function code, details refer to the up table.
Page 115
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 1.5 Wired controller installation Accessory of wired controller Accessory name Quantity Remarks Wired controller With cover. Wood mounting screw M4×20, for mounting on the wall. Mounting screw M4×25, for mounting on the electrical switch box.
Page 116
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz ※ Turn a screwdriver at the concave on bottom panel of the wired controller to remove the back cover. ※ Fix the back cover on the wall or switch box according to the following picture. When...
Page 117
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 2. Wired Controller: KJR-29B1/BK-E (Customized) KJR-29B1/BK-E 2.1 Wired controller specifications Model KJR-29B1/BK-E Power Supply Voltage 5.0V DC Ambient Temperature Range -5° C~43° C Ambient Humidity Range RH40%~RH90% Performance Features 1. Operating mode: Cool, heat, dry, fan and auto.
Page 118
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz 2.2 Wired controller outlook 2.3 Operation instructions 1) Remote signal receiving function: the wired controller can be a remote signal receiving device, it is possible to use the wireless remote controller to control the air conditioner through the wired controller when the system have been powered on.
Page 119
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 3) Set the operating mode Press the mode button to set the operating mode, after each button press the operating mode will circle as follow: 4) Fan speed setting Under COOL, HEAT and FAN modes, press the fan speed button can adjust the fan speed setting.
Page 120
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz Under the timer on setting status, press the timer/clock setting button , then enter into the timer off setting status, and the screen will display The setting method of timer off is the same as the timer on.
Page 121
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 Simultaneously press the temperature adjusting buttons again can cancel the locking state. 10) Air filter cleaning reminding function The wired controller records the total running time of the indoor unit, when the accumulated...
Page 122
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz Installation by other persons may lead to imperfect installation, electric shock or fire. Improper installation may lead to electric shock or fire. A random disassembly may cause abnormal operation or heating, which may result in fire.
Page 123
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 4) Installation procedure The installation manual contains information about the procedure of installing wired controller. Please refer to indoor unit installation manual for connecting between wired controller and indoor unit.
Page 124
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz Wiring principle sketch: Wiring figure: Connect two terminals of embedded 4-core shielding wire with the switching wires of wired controller and signal receiving board. Make sure the sequence of 4 terminals (A, B, C and D) should correspond to the wire sequence of signal switching wires (A, B, C and D).
Page 125
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 Use three M4×20 screws to directly install the back cover on the wall. Use two M4×25 screws to install the back cover on the 86 electrician box, and use one M4×20 screws for fixing on the wall.
Page 126
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz Over fasten the screw will lead to deformation of back cover. Neaten the wires of the wired controller There are three positions of signal wire outlet around the wired controller, when the wired controller directly is installed on the flat wall.
Page 127
Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707 Wired controller’s front cover installation: After adjusting the front cover and then buckle the front cover. Avoid clamping the communication switching wire during installation. Correct install the back cover and firmly buckle the front cover and back over, otherwise will make the front cover drop off.
Page 128
MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz The parameter setting table First Second code Function code Cooling-only/Heat pump Cooling Heat pump (Default) selection only Indoor unit communication Yes (Default) None address setting Power-off memory Yes (Default) None...
Page 129
MCAC-UTSM-201707 Commercial Air Conditioner Division Midea Group Add.: Midea Headquarters Building, 6 Midea Avenue, Shunde, Foshan, Guangdong, China Postal code: 528311 Midea CAC After-service Application Midea CAC News Application Tel: +86-757-26338346 Fax: +86-757-22390205 cac.midea.com global.midea.com Note: Product specifications change from time to time as product improvements and developments are released and may vary from those in this document.