7 Special Control

7.1 Oil Return Operation

In order to prevent compressors from running out of oil, the oil return operation is conducted to recover oil that has
flowed out of the compressor(s) and into the piping system. This operation is performed for all units including units that
are in standby. When the outdoor unit is running in oil return, the digital display on outdoor main PCB will display "d0".

Timing of oil return operation:

 When the initial cumulative operating time reaches 140 minutes and then every 8 hours.
Tables 3-7.1 and 3-7.2 show component control during oil return operation in cooling mode.
Table 3-7.1: Outdoor unit component control during oil return operation in cooling mode
Component
Inverter compressor A
Inverter compressor B
DC fan motor A
DC fan motor B
Electronic expansion valve A
Electronic expansion valve C
Four-way valve
Solenoid valve (oil balance)
Solenoid valve (fast defrosting)
Solenoid valve (EXV bypass)
Solenoid valve (indoor units
bypass)
Solenoid
valve
(inverter
compressor A vapor injection)
Solenoid
valve
(inverter
compressor B vapor injection)
Solenoid
valve
(inverter
compressor B pressure balance)
Table 3-7.2: Indoor unit component control during oil return operation in cooling mode
Fan
Electronic expansion valve
Wiring
8-12HP
14-18HP
diagram label
COMP(A)
COMP(B)
FANA
FANB
EXVA
EXVC
ST1
SV4
SV5
SV6
SV7
SV8A
SV8B
SV9
Component
Unit state
Thermo on
Standby
Thermo off
Thermo on
Standby
Thermo off
20-24HP
26-28HP
Control functions and states
Remote controller setting
Off
Off
Normal control
300 (steps)
300 (steps)
V6-i VRF 50/60Hz
30-32HP
Control functions and states
Fixed frequency
Fan speed controlled according
to discharge pressure
Position 480 (steps) or 3000
(steps)
Position 96 (steps)
Off
Normal control
On
On
Normal control
Controlled according to inverter
compressor A
Controlled according to inverter
compressor B
Open
before
compressor
startup
B