Communication Via Usb; Wiring Process - Ingeteam INGECON SUN 1Play TL M U Series Installation And Operation Manual

Hide thumbs Also See for INGECON SUN 1Play TL M U Series:
Table of Contents

Advertisement

Available languages

Available languages

Communication via USB

13. Communication via USB
These units can communicate locally with a PC via USB using the plant management software INGECON SUN
Manager, available on the Ingeteam website (www.ingeteam.com).

13.1. Wiring process

1.
Remove the cover from the USB Type B connector. Connect the cable to the inverter (cable not supplied
by Ingeteam).
2.
Connect the Cable to a USB port of the PC.
3.
The PC will recognize the device and install its driver. If it is necessary to install the driver manually, it
can be downloaded from following link: http://www.ftdichip.com/Support/Documents/InstallGuides.htm.
4.
Once the installation process has finished, open the device administrator from the control panel.
5.
In the element Ports (COM & LPT) a new COMx port, related to the inverter, will be shown. This will be
determined as USB Serial Port or FTDI USB Serial Port (this will depend on the version of the driver
installed).
6.
Run the INGECON SUN Manager software indicating the port number in the previous step.
To maintain the protection rating of the unit after this task you must always replace the cover over
the USB connector.
While the inverter remains connected by USB the protection rating of the unit is lower than that
specified throughout this document.
ABE2013IQM01_ - Installation and Operation Manual
Ingeteam
EN
ES
37

Advertisement

Chapters

Table of Contents
loading

Table of Contents