Jog Operation - Mitsubishi Electric 800 Series Instruction Manual

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

9.5

JOG operation

The frequency and acceleration/deceleration time for JOG operation can be set.
JOG operation can be used for conveyor positioning, test operation, etc.
Pr.
Name
15
Jog frequency
D200
16
Jog acceleration/
F002
deceleration time
These parameters can be selected from among simple mode parameters when the LCD operation panel (FR-LU08) is
connected to the inverter.
*1
60 Hz is initially set in Pr.20 in Group 1, and 50 Hz in Group 2. (Refer to
 JOG operation by inputting signals (JOG signal and JOG2 signal)
• Operation can be started and stopped by the start signals (STF and STR signals) when the Jog operation selection (JOG)
signal or Jog operation selection 2 (JOG2) signal is ON. (For the operation method, refer to
• The JOG signal can be input only via a control terminal. For the JOG signal, set "5" to any parameter from Pr.178 to Pr.184
(Input terminal function selection)to assign the function to a control terminal.
• The JOG2 signal can be input via a control terminal or via communication. For the JOG2 signal, set "30" to any parameter
from Pr.178 to Pr.189 (Input terminal function selection) to assign the function to a control terminal.
• Use the JOG acceleration/deceleration time function (Pr.16) to set the acceleration/deceleration time for JOG operation.
Output frequency(Hz)
Pr.20
Pr.15
setting range
JOG/JOG2 signal
Forward rotation STF
Reverse rotation STR
 JOG operation using the operation panel
• When the operation panel is in the JOG operation mode, the motor jogs only while a key for start command is pressed.
(For the operation method, refer to
NOTE
• The reference frequency during acceleration/deceleration depends on the Pr.29 Acceleration/deceleration pattern
selection setting. (Refer to
• The Pr.15 setting should be equal to or higher than the Pr.13 Starting frequency setting.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
• During JOG operation, the second acceleration/deceleration function using the RT signal is disabled. (Other second functions
are enabled (refer to
• When Pr.79 Operation mode selection = "4", JOG operation is started by one push of the RUN key on the operation panel
and stopped by the STOP/RESET key.
• This function is invalid when Pr.79 = "3".
Parameters referred to
Pr.13 Starting
frequencypage 175
200
9. (D) Operation Command and Frequency Command
9.5 JOG operation
Initial
Setting range
value
5 Hz
0 to 590 Hz
0.5 s
0 to 3600 s
Forward
rotation
Reverse
rotation
Pr.16
ON
ON
ON
page
45.)
page
169.)
page
298).)
Set the frequency for JOG operation.
Set the motor acceleration/deceleration time during JOG operation.
The acceleration/deceleration time is a period of time that the
inverter takes to increase/decrease the output frequency to the
frequency set in Pr.20 Acceleration/deceleration reference
*1
frequency
.
The acceleration/deceleration times cannot be set separately.
page
50).
Time
Description
page
44.)

Advertisement

Table of Contents
loading

Table of Contents