NOTE
• During acceleration/deceleration, the frequency within the set area is valid.
• If the setting ranges of individual groups (1A and 1B, 2A and 2B, 3A and 3B) overlap, Parameter write error (Er1) occurs.
• If a jump frequency that exceeds the setting of Pr.1 (Pr.18) Maximum frequency is set for the 3-point frequency jump, the
maximum frequency setting is the set frequency. If the jump frequency is less than the setting of Pr.2 Minimum frequency,
the jump frequency is the set frequency. (The set frequency can be equal to or less than the frequency lower limit.)
Example when the frequency upper/lower limit the jump areas.
Output frequency
Pr.32
Maximum frequency (Pr.1)
Pr.31
Maximum frequency and frequency jump
Parameters referred to
Pr.1 Maximum frequency, Pr.2 Minimum frequency, Pr.18 High speed maximum
Pr.32
Minimum frequency (Pr.2)
Pr.31
Set frequency
frequencypage 219
10.9 Avoiding machine resonance points (frequency jump)
Output frequency
Set frequency
Minimum frequency and frequency jump
10.(H) Protective Function Parameters
1
2
3
4
5
6
7
8
9
10