• For the terminal used for the SLEEP signal, set "70" (positive logic) or "170" (negative logic) in any parameter from Pr.190
to Pr.196 (Output terminal function selection).
Deviation
Pr.577 - 1000%
Output frequency
Pr.576
RUN
PID
SLEEP
Deviation
Pr.577 - 1000%
Output frequency
Pr.576
RUN
PID
SLEEP
*1
When the PID output shutoff release level is reached during a deceleration stop, output shutoff is released, operation is re-accelerated and PID
control is continued. During deceleration, Pr.576 Output interruption detection level is invalid.
 Integral stop selection when the frequency is limited (Pr.1015)
• The operation for the integral term can be selected when the frequency or the manipulated amount is limited during PID
control.
• The manipulation range can be selected.
Pr.1015 setting
0 (initial value)
1
2
*1
When the frequency reaches the upper limit, or when the PID manipulated amount reaches 100%, the integral stops and the integral term is
retained. When the frequency decreases, the integral does not stop until the manipulated amount reaches -100%, regardless of the output
frequency.
When Pr.554="0 to 3", reverse operation (Pr.128="10")
Less than Pr.575
Pr.575 or more SLEEP period
When Pr.554="10 to 13", reverse operation (Pr.128="10")
Deceleration stop
Less than Pr.575
Pr.575 or more
Operation at limited frequency
Integral stop
*1
Integral does not stop.
Integral stop
OFF
ON

SLEEP period
OFF
ON
Range of manipulation
-100% to +100%
0% to 100%
Cancel
level
Time
Cancel
level
Time
14.(A) Application Parameters
14.4 PID control
11
12
13
14
15
16
17
18
19
20