 Motor settings (575 V class)
• Refer to the following list and set the parameters according to the applied motor.
Pr.71
Pr.450
0 (Pr.71 initial value) Standard motor
10
8090
9090
3
13
8093
9093
5
15
6
16
9999
(initial
value)
NOTE
• Regardless of the Pr.71 (Pr.450) setting, offline auto tuning can be performed according to Pr.96 (Pr.463) Auto tuning
setting/status. (Refer to
 Using two types of motors (RT signal, Pr.450)
• When using two types of motors with one inverter, set Pr.450 Second applied motor.
• The setting value "9999" (initial value) disables the second motor.
• If Pr.450 ≠ 9999, the following parameters will be enabled by turning ON the Second function selection (RT) signal.
306
13.(C) Motor Constant Parameters
13.1 Applied motor
Motor
Constant-torque motor
IPM motor
SPM motor
Standard motor
Constant-torque motor
IPM motor
SPM motor
Standard motor
Constant-torque motor
Standard motor
Constant-torque motor
No second applied motor
page 309
for offline auto tuning.)
Motor constant value range when performing
offline auto tuning (increment)
Pr.82 (Pr.455), Pr.859 (Pr.860)
• 0 to 500 A, 9999 (0.01 A)
Pr.90 (Pr.458), Pr.91 (Pr.459)
• 0 to 50 Ω, 9999 (0.001 Ω)
Pr.92 (Pr.460), Pr.93 (Pr.461) (Induction motor)
• 0 to 6000 mH, 9999 (0.1 mH)
Pr.92 (Pr.460), Pr.93 (Pr.461) (PM motor)
• 0 to 650 mH, 9999 (0.01 mH)
Pr.94 (Pr.462)
• 0% to 100%, 9999 (0.1%)
Pr.706 (Pr.738)
• 0 to 5000 mV (rad/s), 9999 (0.1 mV/(rad/s))
Pr.82 (Pr.455), Pr.859 (Pr.860), Pr.90 (Pr.458),
Pr.91 (Pr.459), Pr.92 (Pr.460), Pr.93 (Pr.461),
Pr.94 (Pr.462), Pr.706 (Pr.738)
• Internal data value 0 to 65534, 9999 (1)
Pr.82 (Pr.455) and Pr.859 (Pr.860)
• 0 to 500 A, 9999 (0.01 A)
Wye
Pr.90 (Pr.458), Pr.91 (Pr.459),
connection
Pr.92 (Pr.460) and Pr.93 (Pr.461)
• 0 to 50 Ω, 9999 (0.001 Ω)
Pr.92 (Pr.460), Pr.93 (Pr.461)
Delta
• 0 to 50 Ω, 9999 (0.001 Ω)
connection
Pr.94 (Pr.462)
• 0 to 500 Ω, 9999 (0.01 Ω)
Electronic thermal O/L
relay function
Constant-
Standard
torque