Parameter list (by parameter number)

For simple variable-speed operation of the inverter, the initial values of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter's setting, change and check can be made
on the operation panel.
NOTE
Simple
Simple
Simple
indicates simple mode parameters. Use Pr.160 User group read selection to indicate the simple mode parameters
only (initial setting is to indicate the extended mode parameters).
• The changing of the parameter settings may be restricted in some operating statuses. Use Pr.77 Parameter write selection
to change the setting of the restriction.
• Refer to
page 416
Notation
[E800]: Available for the standard model.
[E800-1]: Available for the FM type inverter (standard model).
[E800-4]: Available for the AM (50 Hz) type inverter (standard model).
[E800-5]: Available for the AM (60 Hz) type inverter (standard model).
[E800-(SC)E]: Available for the Ethernet model and the safety communication model.
[E800-SCE]: Available for the safety communication model.
[E800-(SC)EPA]: Available for the Protocol group A (Ethernet model / safety communication model).
[E800-(SC)EPB]: Available for the Protocol group B (Ethernet model / safety communication model).
[200/400 V class]: Available for the 200/400 V class inverters.
[575 V class]: Available for the 575 V class inverters.
[3-phase]: Available for the three-phase power input model.
 Pr.0 to Pr.99
Pr.
Function
Pr.
group
0
G000
1
H400
2
H401
3
G001
4
D301
5
D302
6
D303
7
F010
8
F011
H000
9
C103
for instruction codes for communication and availability of parameter copy, Parameter clear, and all clear.
Name
Torque boost
Simple
Simple
Simple
Maximum frequency
Simple
Simple
Simple
Minimum frequency
Simple
Simple
Simple
Base frequency
Simple
Simple
Simple
Multi-speed setting (high
speed)
Simple
Simple
Simple
Multi-speed setting (middle
speed)
Simple
Simple
Simple
Multi-speed setting (low
speed)
Simple
Simple
Simple
Acceleration time
Simple
Simple
Simple
Deceleration time
Simple
Simple
Simple
Electronic thermal O/L
relay
Simple
Simple
Simple
Rated motor current
Simple
Simple
Simple
Minimum
Setting range
setting
increments
0% to 30%
0.1%
0 to 120 Hz
0.01 Hz
0 to 120 Hz
0.01 Hz
0 to 590 Hz
0.01 Hz
0 to 590 Hz
0.01 Hz
0 to 590 Hz
0.01 Hz
0 to 590 Hz
0.01 Hz
0 to 3600 s
0.1 s
0 to 3600 s
0.1 s
0 to 500 A
0.01 A
3.2 Parameter list (by parameter number)
Initial
Refer
Customer
*1
value
to page
setting
Gr.1
Gr.2
*2
6%
*2
5%
*2
384
4%
*2
3%
*2
2%
120 Hz
219
0 Hz
219
60 Hz 50 Hz
386
60 Hz 50 Hz
202
30 Hz
202
10 Hz
202
*3
5 s
164
10 s
*3
5 s
164
10 s
206,
Inverter rated
309,
current
318