Mitsubishi Electric 800 Series Instruction Manual page 240

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Increment
Monitor item
and unit
32-bit cumulative
1 kWh
energy (lower 16 bits)
32-bit cumulative
1 kWh
energy (upper 16 bits)
32-bit cumulative
0.01 kWh
energy (lower 16 bits)
32-bit cumulative
0.01 kWh
energy (upper 16 bits)
BACnet valid APDU
counter
1
PID manipulated
0.1%
amount
Dancer main set
*15
0.01 Hz
speed
*1
The monitor code is used for the Mitsubishi inverter protocol, CC-Link, CC-Link IE TSN, and CC-Link IE Field Network Basic.
*2
The monitor code is used for the MODBUS RTU, MODBUS/TCP, and BACnet/IP.
*3
Indication with a minus sign is not possible via RS-485 communication (Mitsubishi inverter protocol or MODBUS RTU).
*4
To monitor the item on the LCD operation panel (FR-LU08) in the monitor mode, use Pr.774 to Pr.776 or the monitor function of the FR-LU08 for
setting.
*5
The cumulative energization time and actual operation time are accumulated from 0 to 65535 hours, then cleared, and accumulated again from 0.
*6
The actual operation time does not increase if the cumulative running time before power OFF is less than an hour.
*7
Since each readout of the output voltage and output current displayed on the operation panel is a 4-digit number, a value of more than "9999" is
displayed as "----".
*8
The inverter regards the output current which is less than the specified current level (5% of the rated inverter current) as 0 A. Therefore, each
readout of an output current and output power may show "0" if a too small-capacity motor is used as contrasted with the inverter capacity and the
output current falls below the specified value.
*9
Available when the plug-in option is connected.
*10 The details of bits for the input terminal status are as follows. (1: ON state, 0: OFF state of a terminal on the inverter. "—" denotes an indefinite
(null) value.)
b15
Standard model
-
-
-
b15
Ethernet model
-
-
-
b15
Safety communication model
-
-
-
*11 The details of bits for the output terminal status are as follows. (1: ON state, 0: OFF state of a terminal on the inverter. "—" denotes an indefinite
(null) value.)
b15
Standard model
-
-
-
b15
Ethernet model
-
-
-
b15 Safety communication model
-
-
-
*12 The details of bits for the option input terminal status 1 are as follows. (1: ON state, 0: OFF state of a terminal on the FR-A8AX.) Every bit is 0
(OFF) when the option is not installed.
b15
X15
X14
X13
*13 The details of bits for the option input terminal status 2 are as follows. (1: ON state, 0: OFF state of a terminal on the FR-A8AX. "—" denotes an
indefinite (null) value.) Every bit is 0 (OFF) when the option is not installed.
b15
-
-
-
*14 The details of bits for the option output terminal status are as follows. (1: ON state, 0: OFF state of a terminal on the FR-A8AY/A8AR. "—" denotes
an indefinite (null) value.) Every bit is 0 (OFF) when the option is not installed.
b15
-
-
-
*15 The increment varies depending on the Pr.53 setting. (Refer to
*16 The monitored values are retained even if an inverter fault occurs. Resetting clears the retained values.
Communication
Pr.
Monitor
Monitor
setting
*1
*2
code 1
code 2
H4D
40277
H4E
40278
H4F
40279
H50
40280
83
H53
40283
91
H5B
40291
97
H61
40297
-
-
RES
-
MRS
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
X12
X11
X10
X9
-
-
-
-
-
-
-
RA3
Negative
indication
*3
(-)
The upper or lower 16 bits of the 32-bit cumulative
energy is displayed on each indication.
Monitoring via communication is available.
The count of valid APDU detection is displayed.
(Available only for the FR-E800-EPA and FR-E800-
SCEPA.)
The PID control manipulated amount is displayed.
(Refer to
page
348.)
The set speed for main speed during the dancer control
operation is displayed.
-
RH
RM
-
-
-
-
-
-
-
-
-
-
SO
ABC
-
SO
-
ABC
-
-
-
ABC
X8
X7
X6
X5
-
-
-
-
RA2
RA1
Y6
Y5
page
234).
11.(M) Item and Output Signal for Monitoring
11.2 Monitor item selection on operation panel or via communication
Description
RL
-
-
STR
STF
-
-
-
DI1
DI0
-
-
-
-
-
-
-
FU
RUN
-
-
-
-
-
-
-
-
X4
X3
X2
X1
-
-
-
-
Y4
Y3
Y2
Y1
11
12
13
14
15
16
17
18
19
b0
b0
20
b0
-
b0
b0
-
b0
-
b0
X0
b0
DY
b0
Y0
239