Mitsubishi Electric 800 Series Instruction Manual page 343

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

 Connection diagram
• Sink logic
• Pr.128 = "20"
• Pr.182 = "14"
• Pr.190 = "15"
• Pr.191 = "14"
• Pr.192 = "16"
*1
Prepare a power supply matched to the power supply specifications of the detector.
*2
The applied output terminals differ by the settings of Pr.190 to Pr.196 (Output terminal function selection).
*3
The applied input terminals differ by the settings of Pr.178 to Pr.189 (Input terminal function selection) Assigning the PID control valid (X14)
signal to an input terminal enables PID control to be performed only when the X14 signal is turned ON.
*4
The AU signal need not be input.
 Selection of deviation value, measured value and set point input method,
and PID action method (Pr.128, Pr.609, Pr.610)
• Using Pr.128, select the input method for the PID set point, measured value detected by the meter, and externally
calculated deviation. Also, select forward or reverse action.
342
14.(A) Application Parameters
14.4 PID control
MCCB
R/L1
Power supply
S/L2
T/L3
Forward
rotation
STF
Reverse
STR
rotation
PID control
RH(X14)
selection
SD
10
Setting
Potentiometer
2
(Set point setting)
5
4
*4
0 24V
Power
supply
AC1φ
200/220V 50/60Hz
Inverter
Motor
U
V
M
W
*3
Upper limit
(FUP)RUN
*2
(FDN)FU
Lower limit
*2
Forward rotation
(RL)ABC
*2
output
Reverse rotation
output
Output signal common
SE
(Measured value) 4 to 20mA
*1
Pump
P
2-wire type
3-wire
type
Detector
-
+
+
-
+
(24V
(OUT)
(COM)