Mitsubishi Electric 800 Series Instruction Manual page 265

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

NOTE
• The RUN signal (positive logic) is initially assigned to the terminal RUN (standard models only).
 Fault output (ALM) signal
• The fault signal (ALM signal) is output when an inverter protective function is activated.
• The ALM signal is assigned to the terminals A, B, and C in the initial status.
Inverter fault occurrence
(trip)
ON OFF
ALM
ON OFF
RES
Reset ON
NOTE
• For details of the inverter faults, refer to the Instruction Manual (Maintenance).
 Input power shutoff like magnetic contactor (Y91 signal)
• The Fault output 3 (Y91) signal is output when a fault originating in the inverter circuit or a connection fault occurs.
• To use the Y91 signal, set "91" (positive logic) or "191" (negative logic) in any parameter from Pr.190 to Pr.196 (Output
terminal function selection) to assign the function to an output terminal.
• The following is the list of faults that output the Y91 signal. (For the details of faults, refer to the Instruction Manual
(Maintenance).)
Inrush current limit circuit fault (E.IOH)
CPU fault (E.CPU)
CPU fault (E.6)
CPU fault (E.7)
Parameter storage device fault (control circuit board) (E.PE)
Parameter storage device fault (main circuit board) (E.PE2)
Output side earth (ground) fault overcurrent (E.GF)
Output phase loss (E.LF)
Brake transistor alarm detection (E.BE)
Internal circuit fault (E.13)
 Changing the special relay function for the PLC function
• For the PLC function, the function of special relays (SM1225 to SM1234) can be changed by setting Pr.313 to Pr.322. (For
the details of the PLC function, refer to the PLC Function Programming Manual.)
Parameters referred to
Pr.13 Starting
frequencypage
264
11.(M) Item and Output Signal for Monitoring
11.6 Output terminal function selection
Time
Reset processing
(about 1s)
Fault type
175,
page 176

Advertisement

Table of Contents
loading

Table of Contents