 Setting the stop-on-contact control
• Make sure that the inverter is in External or Network operation mode. (Refer to
• Select either Real sensorless vector control (speed control) or Advanced magnetic flux vector control.
• Set "1 or 11" in Pr.270 Stop-on-contact control selection.
• Set the output frequency for stop-on-contact control in Pr.6 Multi-speed setting (low speed).
Set the frequency as low as possible (about 2 Hz). If a frequency higher than 30 Hz is set, it operates with 30 Hz.
• When both the RT and RL signals are switched ON, the inverter enters the stop-on-contact control, and operation is
performed at the frequency set in Pr.6 independently of the preceding speed.
• Setting Pr.270 = "11" disables stall prevention stop (E.OLT) during stop-on-contact control (with both RL and RT signals
ON).
NOTE
• By increasing the Pr.275 setting, the low-speed (stop-on-contact) torque increases, but overcurrent fault (E.OC[]) may occur
or the machine may oscillate in stop-on-contact status.
• The stop-on-contact function is different from the servo-lock function, and if used to stop or hold a load for an extended period,
this function can cause the motor to overheat. After a stop, immediately switch to a mechanical brake to hold the load.
• Under the following operating conditions, the stop-on-contact function is invalid:
PU operation (Pr.79), JOG operation (JOG signal), PU + External operation (Pr.79), PID control function operation (Pr.128),
Remote setting function operation (Pr.59), Automatic acceleration/deceleration operation (Pr.292), Start time tuning
 Function switching of stop-on-contact control selection
Normal operation (Either RL or RT is OFF or both
Main functions
Real sensorless vector
Output frequency
Multi-speed, 0 to 5 V, 0 to 10 V, 4 to 20 mA, etc.
Stall prevention operation
level
Torque limit level
Pr.22 setting
Excitation current low-speed
scaling factor
Carrier frequency
Pr.72 setting
Fast-response current limit
 Set frequency and validity of the stop-on-contact control (Pr.270 = "1 or
11")
• The following table lists the frequencies set when the input terminals (RH, RM, RL, RT, JOG) are selected together.
• Stop-on-contact control is disabled when remote setting function is selected (Pr.59 = 1 to 3).
are OFF.)
Advanced magnetic flux
control
vector control
Pr.22 setting
Enabled
page
180.)
Stop-on-contact control (Both RL and RT are ON.)
Real sensorless vector
Advanced magnetic flux
control
Pr.6 setting
The smaller value set in
either Pr.22 or Pr.48
Pr.22 setting
The current is compensated by Pr.275 (0% to 300%)
setting from normal operation.
When output frequency is 3 Hz or lower,
Pr.276 setting (Pr.72 when Pr.276 = "9999")
Disabled
14.(A) Application Parameters
14.2 Stop-on-contact control
11
12
13
14
15
16
17
18
vector control
19
20
335