A separate disconnect switch meeting over-voltage category III conditions with proper
capacity fuses or breakers must be installed at a convenient location between the
fryer and the power source. It should be an insulated copper conductor rated for 600
volts and 90° C. For runs longer than 50 feet (15.24 m), use the next larger wire size.
2 2 . . 6 6 I I n n t t e e r r n n a a t t i i o o n n a a l l E E l l e e c c t t r r i i c c a a l l R R e e q q u u i i r r e e m m e e n n t t s s
F F o o r r e e q q u u i i p p m m e e n n t t w w i i t t h h C C E E m m a a r r k k o o n n l l y y ; ; t t o o p p r r e e v v e e n n t t e e l l e e c c t t r r i i c c
s s h h o o c c k k h h a a z z a a r r d d t t h h i i s s a a p p p p l l i i a a n n c c e e m m u u s s t t b b e e b b o o n n d d e e d d t t o o o o t t h h e e r r
a a p p p p l l i i a a n n c c e e s s o o r r t t o o u u c c h h a a b b l l e e m m e e t t a a l l s s u u r r f f a a c c e e s s i i n n c c l l o o s s e e p p r r o o x x i i m m i i t t y y
t t o o t t h h i i s s a a p p p p l l i i a a n n c c e e w w i i t t h h a a n n e e q q u u i i p p o o t t e e n n t t i i a a l l b b o o n n d d i i n n g g c c o o n n d d u u c c t t o o r r . .
T T h h i i s s a a p p p p l l i i a a n n c c e e i i s s e e q q u u i i p p p p e e d d w w i i t t h h a a n n e e q q u u i i p p o o t t e e n n t t i i a a l l l l u u g g f f o o r r
t t h h i i s s p p u u r r p p o o s s e e . . T T h h e e e e q q u u i i p p o o t t e e n n t t i i a a l l l l u u g g i i s s m m a a r r k k e e d d w w i i t t h h t t h h e e
f f o o l l l l o o w w i i n n g g s s y y m m b b o o l l . .
• CE units require a minimum wire size of 4 mm to be wired to
• The supply power cords shall be oil-resistant, sheathed
NOTICE
:
• It is recommended that a 30 mA rated protective device such
Units being used outside the United States may not be shipped with the power cord
attached to the unit because of the different wiring codes. The fryers are available
from the factory wired for 200, 240, 380 and 415 volts, 3 phase, 50 Hertz service. A
terminal block is mounted inside the fryer for the cable wiring.
the terminal block. If a flexible power cord is used, it must be
HO7RN type.
flexible cable, no lighter than ordinary polychloroprene or
other equivalent synthetic elastomer-sheathed cord.
as a residual current circuit breaker (RCCB), or ground fault
circuit interrupter (GFCI), be used on the fryer circuit.