Installing the template and mounting bolt anchors
Procedure for
installing
cabinet bolt
anchors
The concrete base must be drilled to accept the M12 anchor bolts. Washers,
bushes and M12 steel bolts must be supplied by the customer.
1.
2.
3.
4.
5.
Inst. 3–14
WARNING
Wear safety glasses and a dust mask when drilling holes.
CAUTION
Drilling concrete flooring produces cement dust, which is
harmful to equipment and wiring. Protect the cabinets and
any nearby equipment from dust. Use a tarpaulin, cloth, or
plastic sheeting to cover exposed equipment. Clean up
any accumulated debris from the anchor installation
carefully before exposing the equipment. Use drilling
equipment suitable for cutting steel reinforced concrete.
Using the four holes in the template as a guide, drill the concrete base to a
depth and clearance for the M12 anchor bolts.
Fit the M12 mounting anchors to the holes in the base.
Fit the anchor bolts with the supplied bushes and washers, through the
template, to each anchor.
Tension up the anchor bolts to expand the anchors.
Remove and retain the M12 bolts and washers for later use.