Motorola Horizonmacro outdoor Installation/Configuration Manual page 191

Table of Contents

Advertisement

GSM-204-423
Power up
procedure with
code load
The following procedure should be carried out to power up the cabinet, with
code load. The code will be provided either direct from the BSC from the E1/T1
line, or from a PCMCIA card installed in the PCMCIA socket of the master
MCUF.
Preparing the cabinet for power up with code load
Proceed as follows to prepare the cabinet prior to power up:
1.
2.
3.
4.
5.
6.
7.
8.
9.
31st Oct 01
CAUTION
This procedure should only be carried out by experienced
field personnel.
Make the E1/T1 connection to BSC.
Insert (optional) PCMCIA card in MCUF PCMCIA socket.
Connect the 9 to 9-way cable from the PC serial A port to MCUF TTY port.
Start the terminal emulator program at the PC.
Change to Level 3, and at the MMI-RAM> prompt type: CTRL N
Set all circuit breakers in both ac distribution boxes and the PSU dc circuit
breaker panel to off.
Set the internal and external battery circuit breakers to off.
Set the switch of each PSM to the OUTPUT DISABLE position.
Press and release all push on/push off circuit breaker buttons to the out
(off) position.