GSM-204-423
Power
requirements
The power requirements of cabinets depends on the configuration.
Power consumption (dc and ac)
Table 2-5 lists typical and maximum power consumption values.
Cabinet input power supply requirements
Table 2-6 lists the power supply requirements for the different power supply
options.
31st Oct 01
Table 2-5 Power consumption of full cabinet, including digital redundancy
and external battery charging
Typical measured consumption
2200 W
NOTE
Maximum power consumption figures are theoretical
values derived under extreme conditions and are affected
by variables such as temperature, component tolerances,
transmission power and supply voltage. Although these
figures must be considered when planning site power
requirements, typical measured consumption values will
be lower.
WARNING
All cabinets and supply cables must be protected by an
upstream fuse or circuit breaker.
Table 2-6 Main outdoor cabinet power requirements
Nominal voltage
110 V ac single phase
230 V ac single phase
230 V ac three phase
and neutral (star)
230 V ac three phase
without neutral (delta)
Installation & Configuration: Horizon macro outdoor
68P02902W03-A
CONTROLLED INTRODUCTION
Site requirements and considerations
Maximum power consumption
5600 W
Supply voltage
and frequency
range
88 to 134 V ac
at 45 to 66 Hz
176 to 265 V ac
at 45 to 66 Hz
176 to 265 V ac
at 45 to 66 Hz
176 to 265 V ac
at 45 to 66 Hz
Current supply
maximum
54.4 A
(at nominal voltage)
26.1 A
(at nominal voltage)
26.1 A
(at nominal voltage)
26.1 A
(at nominal voltage)
Inst. 2–3