Removing Sfp Devices - Emerson PACSystems RX3i User Manual

Profinet i/o-controller
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

RSTI-EP PROFINET I/O Controller User Manual
GFK-2571R
Typical SFP Modules
Below are images of the two types of Ethernet SFPs. The Single- and Multi-Mode Fiber SFPs
accept an LC Connector. The Copper SFPs accept an RJ45 connector
Figure 29: Fiber SFP showing LC Connector
Figure 30: Copper SFP showing RJ45 Connector
2.7.4

Removing SFP Devices

WARNING
If the surrounding air operating temperature of the PNC001 module is greater than 40°C
(104°F), SFP devices could reach operating temperatures over 70°C (158°F). Under these
conditions, for your safety, do not use bare hands to remove an SFP device from the SFP
cage. Use protective gloves or a tool (needle-nose pliers) to avoid handling the hot SFP
device directly when removing the SFP device.
Remove the cable from the SFP device. If the device has a latching mechanism such as a bale
clasp, open it gently. Do not pull on the latching mechanism. Hold the sides of the SFP
device and pull it out of the PROFINET Controller port.
Installation
Section 2
May 2021
40