Adding Versamax Modules To A Remote Node - Emerson PACSystems RX3i User Manual

Profinet i/o-controller
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

RSTI-EP PROFINET I/O Controller User Manual
GFK-2571R
Adding power supplies to the configuration sets up power supply alarms. Alarms will be
triggered if the power supply is configured but not working or configured in the wrong
subslot. These power supplies have no configurable parameters, but their power supply and
GSDML details can be viewed by double-clicking on a power supply icon or right-clicking and
selecting Configure.
3.7.3

Adding VersaMax Modules to a Remote Node

The PNS remote node can contain the module types listed in the VersaMax PROFINET
Scanner Manual, GFK 2721. However, it cannot contain the following expansion modules or
communications modules:
Unsupported VersaMax Modules
Asi Network Master Module
Device Net Network Control Module
Expansion Transmitter Module
Expansion Receiver Module, Isolated
Expansion Receiver Module, Non-isolated
Profibus-DP Network Slave Module
To add a module to the remote node, right click on the VersaMax PNS icon in the Navigator
and select Change Module List. In the right pane of the Change Module List window, expand
the list of VersaMax module types.
Figure 65: Adding VersaMax I/O Modules to Remote Node
Select modules from the list (right pane) and drag them to available slot locations in the
remote node (left pane).
Configuration
IC200BEM104
IC200BEM103
IC200ETM001
IC200ERM001
IC200ERM002
IC200BEM002
Section 3
May 2021
70