Configuration Tools

PAC Machine Edition is the primary tool used to configure an RX3i PROFINET network. In
addition, for the PNC001 module only, certain parameters can be set from a computer
through the Command Line Interface (CLI).
The Command Line Interface can be used to set the non-volatile parameters in the PNC001-
Ax module, as listed below. These parameters are initially set up in the PAC Machine Edition
configuration. If any of these parameters is subsequently changed using CLI, the PNC001
module uses the new setting. Regardless of their source, the PNC001 module retains these
settings in non-volatile memory, thus ensuring they can be re-asserted following a power
cycle.
3.2.1

Non-Volatile Configuration Parameters

Parameter
IP Address
Subnet Mask
Default Gateway
Device Name
Redundant Media Role
Redundant Media Ring
Port 1 ID
Redundant Media Ring
Port 2 ID
Redundant Media test
interval
Redundant Media
monitor count
3.3

Configuring an RX3i PROFINET Controller

3.3.1
Configuring a Rack-Mounted RX3i PROFINET
Controller (PNC001)
The PNC001-Bxxx is backward compatible with the PNC001-Ax. No hardware
configuration changes to an existing application are required when replacing a PNC001-Ax
with PNC001-Bxxx. The PNC001-Bxxx has a lower power consumption than a -Ax .
Therefore, new applications should use the PNC001-Bxxx hardware configuration so that
PME's power calculation is more accurate. Use of the PNC011-Bxxx also provides
customers access to future upgrades as features are added to the PNC001-Bxxx.
Configuration
Description
IP Address of the PNC001.
Subnet mask of the PNC001.
Default Gateway for the PNC001.
PNC001's PROFINET Device Name. Defaults to empty
string - indicating the PNC001 is not named.
Specifies whether media redundancy is disabled, or if it
is enabled as a Client, or if it is enabled as a Manager.
Indicates one of the two network ports involved in
Media Redundancy. Valid values are 1 to 4.
Indicates one of the two network ports involved in
Media Redundancy. Valid values are 1 to 4.
Interval for sending test frames on ring ports in
millisecond units. Valid values are 1 to 1000 ms.
Indicates the number of consecutive failed test frames
before declaring a ring failure. Valid values are 2 to 10.
Section 3
May 2021
Default
Value
0.0.0.0
0.0.0.0
0.0.0.0
""
Disabled
1
2
20 ms
3