The USB ports on the CPUs that support embedded PROFINET operate independently of the
PROFINET function. Refer to the corresponding product documentation for further details.
The PNC001-Bxxx module has no micro USB port, and therefore does not support the
Command Line Interface.
The PNC001-Ax module has a micro USB port for connection to a computer running
Windows® 2000, Windows XP, Windows Vista®, Windows 7 or Windows 10. On the
PNC001 module (-Ax version) only, the USB port can be used to access the Command Line
Interface (CLI) function using a terminal emulation application such as HyperTerminal.
The Command Line Interface function can be used to monitor a PROFINET Controller
module and check its operation. If a problem occurs, the Command Line Interface can be
used help determine the cause.
A driver-install application is provided to set up a computer to communicate with the USB
port (see Section 2:, Installation, for instructions).
1.5.4

Reset Pushbutton

The Reset pushbutton on a PNC001 module can be used to manually reset the module
without cycling power. The restart operation commences when the pushbutton is released.
1.5.5

LEDs on the CPUs with Embedded PROFINET

Refer to the corresponding product documentation for further details.
1.5.6

LEDs on the PNC001 Module

The table below summarizes LED functions on the PNC001 module. More detailed
information about error indications and special blink patterns is given in Section 2:,
Installation and Section 5:, Diagnostics
OK
LAN
STATUS
CONFIG
ACTIVE
USB
Port LEDs
Introduction
Green ON indicates that the module can perform normal operation.
Indicates network packets are being processed by the network interface (not just
passing through the embedded switch).
Indicates the condition of the PROFINET Controller during normal operation. It
indicates whether an entry other than the start-up event is present in the module's
Local Log. STATUS can also indicate whether any of the MAC addresses are invalid.
Indicates whether the module has received its configuration from the RX3i CPU.
Indicates the status of PROFINET connections.
Indicates activity on the USB port. (PNC001-Ax only)
Indicate link speed, link connection and link activity corresponding to the four
possible external Ethernet ports.