Emerson PACSystems RX3i User Manual page 74

Profinet i/o-controller
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

RSTI-EP PROFINET I/O Controller User Manual
GFK-2571R
When the PNS does not support PROFINET System Redundancy, or is not configured in an
HSB CPU Redundancy system, the PNS Programmer automatically selects simplex
operation (non-redundant control) by setting the Redundancy Mode parameter to None.
To configure a redundancy-capable PNS for simplex operation within an HSB CPU
Redundancy system, change the Redundancy Mode parameter on the Redundancy tab
from HSB CPU Redundancy to None.
PROFINET Scanner Parameters (Media Redundancy Tab)
By default, the PNS is not set up for Media Redundancy. If the system will use Media
Redundancy (see Section 6:, Redundant Media, for more information), open the Media
Redundancy tab and select Client.
Figure 57: PNS Parameters Media Redundancy Tab
If the PNS will be a Media Redundancy Client, click on Ring Port 1 and Ring Port 2 to choose
the module ports that will be used.
Figure 58: Select PNS Ring Ports Usage
PROFINET Scanner Parameters (Module Parameters Tab)
The PNS has one module parameter:
Figure 59: PNS Parameters Module Parameters Tab
By default, the PNS module LEDs will blink a fault code if a fatal error occurs. This can be
changed to cause the PNS to restart instead.
Configuration
Section 3
May 2021
67