PACSystems™ RX3i PROFINET Controller
IC695PNC001-BEBD
Firmware Version 3.20
1
Includes conformal coat and low temperature module variants, if available.
2
The last two characters of the catalog number suffix may not increment with every firmware release beginning with IC695PNC001-BCBD Release 3.15.
1 2
IMPORTANT PRODUCT INFORMATION
GFK-2573AB
Jul 2022

Advertisement

Table of Contents
loading

Summary of Contents for Emerson PNC001-A Series

  • Page 1 IMPORTANT PRODUCT INFORMATION GFK-2573AB Jul 2022 PACSystems™ RX3i PROFINET Controller IC695PNC001-BEBD Firmware Version 3.20 Includes conformal coat and low temperature module variants, if available. The last two characters of the catalog number suffix may not increment with every firmware release beginning with IC695PNC001-BCBD Release 3.15.
  • Page 2 Changes, modifications, and/or improvements to equipment and specifications are made periodically and these changes may or may not be reflected herein. It is understood that Emerson may make changes, modifications, or improvements to the equipment referenced herein or to the document itself at any time. This document is intended for trained personnel familiar with the Emerson products referenced herein.
  • Page 3: Ordering Information

    Ethernet traffic such as ping and telnet. Features of the RX3i PNC001 include: ▪ Full configuration services for the RX3i PROFINET Controller, plus all connected Emerson and third-party I/O- Devices using PAC Machine Edition (PME). ▪...
  • Page 4 GFK-2573AB Jul 2022 Specifications: PNC001 Specifications Descriptions PROFINET Support PROFINET Version 2.2 General Class A I/O-Controller. Redundantly controlled operation conforms to PROFINET V2.3 Type S-2 System Redundancy. RX3i CPU Compatibility See the Functional Compatibility section. Power Requirements PNC001-Ax PNC001-Bxxx 3.3 Vdc: 0.6 A with no SFP devices 3.3 Vdc: 0.5 A with no SFP devices 1.3 A maximum 1.2 A maximum...
  • Page 5: Emc Installation Requirements

    GFK-2573AB Jul 2022 Programmer Limits Number of I/O-Controllers 128 (32 RX3i CPU targets × 4 IO-Controllers per RX3i CPU) Number of I/O-Devices 4080 (255 per network × 16 PROFINET networks) Total number of devices 4208 (does not include backplanes, power supplies, or I/O modules) Hot-swappable For product standards, general operating specifications, and installation requirements, refer to PACSystems RX3i System Manual, GFK-2314.
  • Page 6: Status Reporting

    GFK-2573AB Jul 2022 ATEX Zone 2 This module must be mounted in an enclosure certified in accordance with EN60079-15 for use in Zone 2, Group IIC, and rated IP54. The enclosure shall only be able to be opened with the use of a tool. Status Reporting The PNC001 provides 32 bits of status information to a configured location in the RX3i CPU’s reference memory.
  • Page 7 GFK-2573AB Jul 2022 LEDs on the PROFINET Controller Module The table below summarizes LED functions. Note that there are differences between the -Ax version and the -Bxxx version. For detailed information refer to Installation and Diagnostics in PACSystems RX3i PROFINET I/O Controller Manual, GFK-2571K or later.
  • Page 8: Quick Start

    GFK-2573AB Jul 2022 Quick Start Before installing and operating the PNC001, refer to PACSystems RX3i PROFINET I/O Controller Manual, GFK-2571 for detailed information. Installation and initial startup procedures for the PNC001 include the following steps: 1. Pre-Installation check 2. Installing the PNC001 in an RX3i backplane The PNC001 must be installed in the main (CPU) rack of the RX3i system, using a Universal Backplane such as IC695CHS007, CHS012, or CHS016.
  • Page 9 GFK-2573AB Jul 2022 4. Installing SFP devices WARNING Optical SFPs use an invisible laser to generate a fiber-optic signal. Always keep the port covered if a cable is not installed. Do not look into the open port if a cable is not installed. WARNING If the surrounding air operating temperature of the PNC001 is greater than 40 ...
  • Page 10: Release History

    2020 Resolved a Loss of Device in an MRP Ring after the IC695PNC001-BCBD 3.16 2020 PNC001-Bxxx is reset. Rebranded the PNC001 to Emerson, applied patches for IC695PNC001- 3.15 VxWorks URGENT/11 vulnerabilities, and made additional BCBD 2019 updates to enhance cyber security.
  • Page 11 GFK-2573AB Jul 2022 Version Firmwar Date Comments Revision Added support for HART ® Pass-Through feature set over PROFINET. A HART-capable PROFINET scanner (IC695PNS001 or IC695CEP001) must also be employed to IC695PNC001-AK 2.20 support the HART-capable RX3i analog modules over 2015 PROFINET.
  • Page 12: New Features And Enhancements

    GFK-2573AB Jul 2022 Upgrades Upgrade Kit: 41G2472-FW01-000-A5 Only IC695PNC001-Bxxx or later revision modules are field upgradable to this release using the upgrade kit listed above. IC695PNC001-Ax modules cannot be upgraded with this kit due to hardware and firmware design changes in the PNC001-Bxxx revision.
  • Page 13 GFK-2573AB Jul 2022 Functional Compatibility The following CPU firmware and programming software versions are required to use the features introduced in PNC001 release 2.00 and later: Subject Feature Minimum Version Required The following minimum backplane hardware revision must be used: IC695CHS012-BAMP IC695CHS016-BAMP IC695CHS012CA-BAMP...
  • Page 14 GFK-2573AB Jul 2022 Subject Feature Minimum Version Required CPE330 Release 8.70 CPU320/CPU315 Release 8.70 CPE310/CPE305 Release 8.70 Extended PROFINET device Subslot Number range CRU320 Release 8.70 CPE302 Release 9.40 (Other CPU models are not supported) CPE330 Release 8.50 CPU320/CPU315 Release 8.50 RX3i PNC001 Release 2.20 CPE310/CPE305 Release 8.50 HART Pass-Through...
  • Page 15 GFK-2573AB Jul 2022 Subject Feature Minimum Version Required Effective with PME 8.6 SIM 3 and PME 8.5 SIM 11 (PPS 2.6 If using PROFINET System SIM3 and PPS 2.5 SIM11), the PNC001 is configured to use Redundancy, users MUST RT Class 2 for redundant PROFINET connections. To meet upgrade the PNC001 specifications, this requires PNC001 firmware 2.2 or later.
  • Page 16 GFK-2573AB Jul 2022 Subject Feature Minimum Version Required RX3i PNC001 Release 2.00 (or later) Hot Standby Redundancy with PROFINET I/O PAC Machine Edition 8.00 SIM 5 Non-Hot Standby Redundancy system using CRU320 RX3i PNC001 Release 2.00 (or later) PAC Machine Edition 7.00 SIM 8 Non-Hot Standby Redundancy system PNC001-Bxxx and PNC001-Ax Hardware Comparison...
  • Page 17 GFK-2573AB Jul 2022 Issue Description Two scenarios can cause the PNC001 to indicate that an MRP Ring is closed when, in fact, it is still open. The scenarios are: 1. When either an RX3i PNS001 or PNC001 that participates in the MRP ring as an MRP Client communicating via Copper or Fiber SFPs is powered-up in the MRP ring, extra Ring Closed/Ring Open faults are logged in the I/O fault table.
  • Page 18 GFK-2573AB Jul 2022 Issue Description Loss of Device faults for currently connected devices may appear in the PLC I/O Unexpected Loss of Device Fault table and/or PNC001 local log when the PNC001 is reset via its reset faults pushbutton. The power flow output of the PNIO_DEV_COMM function block provides validation of the input parameters and confirms that the PNC001 has locally Unintended operation of processed the configuration of the specified I/O Device.
  • Page 19 GFK-2573AB Jul 2022 Restrictions and Open Issues related to the Command Line Interface (-Ax Version Only) Restriction/Open Issues Description Occasionally, the CLI will return invalid help suggestions if the user attempts to get help on an invalid command by using the question mark key. Attempting to issue the command based on this help text will result in an Error: Bad command response from Invalid help response for invalid the CLI.
  • Page 20: Operational Notes

    GFK-2573AB Jul 2022 Operational Notes Operational Note Description When storing Media Redundancy Protocol (MRP) configuration updates to an operating MRP ring network, users may infrequently observe one or more pairs of Loss of Device and subsequent Addition of Device faults regarding PROFINET I/O Device faults on the network. This is expected behavior and is more likely to occur on ring networks with a large number Storing updated media of PROFINET I/O Devices acting as MRCs with very fast I/O Update Rates configured.
  • Page 21 GFK-2573AB Jul 2022 Operational Note Description Beginning with PME 8.60, the PROFINET DCP tool requires elevation to administrator privilege to run when it is launched by right-clicking on a PNC001. Since the PME installation does not set up PME or any of its internal tools to run at the administrator privilege level, you will have to inform Windows that you want it to run PME as an administrator.
  • Page 22: Additional Information

    GFK-2573AB Jul 2022 Additional Information For additional information, please refer to the manuals listed below. Manuals can be downloaded from the Support website. Please see the link located at the end of this document. PACSystems RX3i PROFINET I/O Controller Manual GFK-2571 PACSystems RX3i PROFINET Controller Command Line Interface Manual GFK-2572...
  • Page 23: General Contact Information

    Note: If the product is purchased through an Authorized Channel Partner, please contact the seller directly for any support. Emerson reserves the right to modify or improve the designs or specifications of the products mentioned in this manual at any time without notice. Emerson does not assume responsibility for the selection, use, or maintenance of any product.