Faults Unique To Local Log Table - Emerson PACSystems RX3i User Manual

Profinet i/o-controller
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

RSTI-EP PROFINET I/O Controller User Manual
GFK-2571R
The PROFINET Controller maintains these entries in its Local Log table. Entries in the Local
Log are preserved across power-cycles. In the PNC001-Ax module, they may also be cleared
using the CLI clear log command.
Clearing the CPU Fault Tables or restarting the PROFINET Controller does NOT clear the Local
Log table.
If the Local Log table overflows, new entries overwrite the oldest entries, which are then lost.
If that happens, CLI indicates the number of entries that have been discarded. The count of
discarded entries is reset to zero whenever the Local Log table is cleared (applies to PNC001
module only).
The STATUS LED on the PNC001-Ax module provides an indication that a new fault has been
added to the module's Local Log since either the last time the module was restarted, or since
the last time the log was cleared. The STATUS LED is ON at power-up, after the Local Log has
been cleared, or after executing the clear statLED command from CLI. When a subsequent
fault occurs, the STATUS LED turns OFF to indicate that a new fault has been logged.
5.8.1

Faults Unique to Local Log Table

The following faults are registered in the Local Log table of the PROFINET Controller and in
no other table. When viewed using the CLI log details command, they have an Entry Type of
Local Fault.
The Local Log Table also contains faults that are passed to the PACSystems CPU. Those
faults, which are listed in the
Diagnostics
Section 5
May 2021
106

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pacsystems rsti-ep

Table of Contents